Maintenance
Before performing maintenance ensure the proper authorities are notified that the
system is undergoing maintenance and will temporarily be out of service. Disable the
zone or system undergoing maintenance to avoid any unwanted alarms.
Prior to commissioning ensure the dust covers are left on the detectors and measures
are taken to keep the detectors free from dust, dampness and corrosion.
Detector should be cleaned at least once a year to ensure normal operation of the
system.
The detector should be tested after any cleaning or when replaced.
Protect the metal component on the PCB against damp and improper distortion.
If nuisance alarms are often found of the detector on site, the sensing chamber should
be cleaned and replaced when necessary.
a) Open the top cover of detector, and draw out the sensing chamber by slightly
lifting its two sides using a flat screwdriver, as shown in Fig. 7.
b) Clean the sensing chamber by using an alcohol
cotton swab, clean water and brush. Please
note not to leave any cotton in the chamber.
c) Re-install the sensing chamber and top cover.
Specifications
Operating Voltage
Standby Current
Alarm Current
Fire LED
Remote indication output
Max. ripple voltage
Alarm Reset
Sensitivity setting
Wiring
Ingress Protection Rating
Environmental Temperature
Relative Humidity
Material
Dimension
Mounting Hole Distance
Weight
Accessories and Tools
Module
Name
P-9910B
Handheld Programmer
DB-01
Base
Ordering information
Part number
Description
DC-9102E-KID
Conventional Photoelectric Smoke Detector
24VDC (12VDC ~28VDC)
≤60mµA
≤55mA
Red, periodical flash when polling when LED status is set to
'ON'. No illumination when the status is set to 'OFF'. Periodical
two flashes when in fault or sensing chamber is dirty. Steady
illumination when in alarm.
Polarity-sensitive output, directly connecting with remote
indicator (built in 10k resistor in series, max. output current is
2mA); no illumination when in nofrmal state; flash when in alarm.
2V (peak to peak value)
Instant power down 910s mon, 1.0VDC max.
The sensitivity can be set by hand held programmer. There are
two sensitivity levels: level 1 (default ) and level 2.
Two-wire, polarity sensitive.
IP2X
-10˚C~+50˚C
≤95%, non-condensing
ABS
Diameter : 100mm
Height : 44.5mm (without base)
45mm ~ 75mm
Approx. 110g
D A T A S H E E T
FIGURE 7
Remarks
Order separately
Order separately
Ship Wt., lb
(kg)
DC-9102E-KID
Issue 1.0