APPEnDix i. oPERATion MoDES AnD TRouBlEShooTinG GuiDE

Modes
*Red
Yellow and
See
Remote
Note
Trouble
Below
Normal
Off
Off
Alignment
Off
On
Alarm
On
Off
Trouble-Drift
Off
3 Quick
Comp Elevated
Blinks
Signal
Trouble-Drift
Off
2 Quick
Comp Reduced
Blinks
Signal
Trouble-Signal
Off
2 Quick
Over Range
Blinks
Trouble-Beam
Off
4 Quick
Blockage
Blinks
Response
Initialization-
Off
Blink until
Power on
complete
Initialization-
Off
Blink until
alignment exit
complete
Local Test
On
Blinks out
(BEAM355SA)
the amount
Pass Result
of drift used.
Local Test
Off
On until
(BEAM355SA)
reset or
Fail Result
time-out
Local Test
Off
On until
(BEAM355A)
reset or
Fail
time-out
Local Test
On
Blinks out
(BEAM355A)
the amount
Pass Result
of drift used.
Note: Green and Red LEDs are controlled by the control panel.
Blinks output by Yellow LED and Remote Trouble Output once the device has
passed a local remote test:
Percent the detector has drifted
<10%
<20%
<30%
<40%
<50%
<60%
<70%
<80%
<90%
<100%
F300-30-00
*Green
Remote
Dual Digital Display
See
Alarm
Note
Below
Blink
Blink
Off
Blink
Blink
On, Relative amount
of signal 0-99, or – if
automatic gain resetting,
or Lo if signal is too low
Off
On
Off
Blink
Blink
Off
Blink
Blink
Off
Blink
Blink
Off
Blink
Blink
Off
Blink
Blink
Off
Blink
Blink
Off
Off
On
Off
Blink
Blink
Off
Blink
Blink
Off
Off
On
Off
Number of blinks output
None
1
2
3
4
5
6
7
8
9
Initiating means
Successful completion of
initialization or detector
reset
Alignment Switch
Smoke, Test Filter,
RTS451 Test Stations
Long Term Drift
Reference Out of Range
Long Term Drift
Reference Out of Range
Increase of Reflected
Signal
Beam Blockage
Apply Power from
discharged state.
Depressing RESET
switch after alignment
Panel or RTS451/KEYA
Panel or RTS451/KEYA
test input
Panel or RTS451/KEYA
test input
Panel or RTS451/KEYA
10
Comments & Troubleshooting Tips
• Sunlight into detector or reflector.
• Re-Align detector.
• Clean detector and reflector.
• Inspect line of sight between detector
and reflector for reflective objects in
the pathway.
• Remove blockage.
• Faulty unit.
Remains in alarm until reset or time-out
Remains in fault until reset or time-out
Remains in fault until reset or time-out
Remains in alarm until reset or time-out