Pre-Alignment Checklist - Honeywell Fire-Lite Alarms BEAM355A Installation And Maintenance Instructions Manual

Single-ended reflected type projected beam smoke detector
Table of Contents

Advertisement

fiGuRE 6. wiRinG connEcTionS AT DETEcToR
T3
T2
fiGuRE 7. wiRinG DiAGRAM
T3
T2
LISTED
+
REMOTE
POWER
SOURCE
+
* Only used for
BEAM355S. See
FROM PANEL OR
electrical ratings.
PREVIOUS DEVICE
F300-30-00
T1
T1
+ –
+
COMMUNICATION LINE
TO NEXT
32 VDC MAX.
DEVICE
TWISTED PAIR IS
RECOMMENDED.
fiGuRE 8. wiRinG DiAGRAM (RTS451)
PIN 1
PIN 2
PIN 4
PIN 3
PIN 5
RTS451/KEY
fiGuRE 9. wiRinG DiAGRAM (RTS451)
SLC (+)
SLC (–)
C0260-01
inSTAllATion / AliGnMEnT
Reference Figures 10 through 14 for installation, alignment, and maintenance.
The alignment of the BEAM355A/BEAM355SA is divided into four steps:
coarse alignment, fine adjustment, final gain adjustment, and final verifi-
cation. It is necessary for all four steps to be executed properly to ensure
proper alignment of the product. If the detector and reflector are mounted per
Mounting Locations and Mounting Instructions sections of this manual and
the alignment procedures are executed properly, false alarms and nuisance
trouble signals will be minimized.

PRE-AliGnMEnT chEckliST

Insure that both the detector and reflector are mounted securely to stable
surfaces.
Insure that all wiring is correct.
Insure that terminal blocks are fully seated into their receptacles on the
detector.
Complete any wiring dressing to minimize movement to the detector
once the alignment procedure is completed.
Insure that the appropriate number of reflectors are used for the in-
stalled distance. Distances between 230 & 328 Feet (70 - 100m) require
additional reflectors (4 total). The BEAMLRK accessory should be used
in these cases.
Insure that the line of sight between the detector and reflector is clear
+
and that reflective objects are not too near. See Mounting Instructions
for more details.
Insure that both the detector and reflector are mounted within their
operational parameters for off axis angles. See Mounting Instructions
C0261-00
for more details.
Disable the zone or system to prevent unwanted alarms before applying
power.
Insure power to the detector is "ON".
Insure that the appropriate address is set on the code wheels.
5
DETECTOR
T1-1
POWER IN +
T1-2
POWER IN –
T2-1
REMOTE ALARM OUT
T2-2
AUX (–)
T2-4
RESET INPUT
T2-3
TEST INPUT
T3-3
REMOTE TROUBLE OUTPUT
OPTIONAL YELLOW LED
BEAM355S
Alarm
Signal
T2-1
Circuit
(Note 1)
T2-2
Note 1: See electrical ratings section of this
manual for circuit output ratings.
POWER OUT +
T1-3
POWER OUT –
T1-4
C0328-01
Red
C0329-00
I56-2543-004R