Appendix I. Operation Modes And Troubleshooting Guide - Honeywell SK-Beam Installation And Maintenance Instructions Manual

Single-ended reflected type projected beam smoke detector
Table of Contents

Advertisement

APPENDIX I. OPERATION MODES AND TROUBLESHOOTING GUIDE

*Red
See
Yellow,
Note
Remote
Modes
Below
Trouble
Normal
Off
Off
Alignment
Off
On
Alarm
On
Off
Trouble: Drift
Off
3 Quick
Compensation,
Blinks
Elevated Signal
Trouble: Drift
Off
2 Quick
Compensation,
Blinks
Reduced Signal
Trouble: Signal
Off
2 Quick
Over Range
Blinks
Trouble: Beam
Off
4 Quick
Blockage
Blinks
Response
Initialization:
Off
Blink until
Power on
complete
Initialization:
Off
Blink until
alignment exit
complete
Local Test
On
Blinking
(SK-Beam-T)
the
Pass Result
amount of
drift used
Local Test
Off
On until
(SK-Beam-T)
reset or
Fail Result
time-out
Local Test
Off
On until
(SK-Beam)
reset or
Fail
time-out
Local Test
On
Blinking
(SK-Beam)
the
Pass Result
amount of
drift used
Note: Green and Red LEDs are controlled by the control panel.
Blinks output by Yellow LED and Remote Trouble Output once the device has
passed a local remote test:
Percent the detector has drifted
<10%
<20%
<30%
<40%
<50%
<60%
<70%
<80%
<90%
<100%
*Green
See
Note
Remote
Below
Alarm
Dual Digital Display
Blink
Blink
Off
Blink
Blink
On, Relative amount
of signal 0-99, or – if
automatic gain resetting,
or Lo if signal is too low
Off
On
Off
Blink
Blink
Off
Blink
Blink
Off
Blink
Blink
Off
Blink
Blink
Off
Blink
Blink
Off
Blink
Blink
Off
Off
On
Off
Blink
Blink
Off
Blink
Blink
Off
Off
On
Off
Number of blinks output
None
1
2
3
4
5
6
7
8
9
Initiating means
Successful completion of
initialization or detector reset
Alignment Switch
Smoke, Test Filter, RTS451/
RTS151 Test Stations
Long Term Drift Reference Out of
Range
Long Term Drift Reference Out of
Range
Increase of Reflected Signal
Beam Blockage
Apply Power from discharged state.
Depressing RESET switch after
alignment
Panel or RTS451, RTS451KEY,
RTS151, or RTS151KEY
Panel or RTS451, RTS451KEY,
RTS151, or RTS151KEY test input
Panel or RTS451, RTS451KEY,
RTS151, or RTS151KEY test input
Panel or RTS451, RTS451KEY,
RTS151, or RTS151KEY
9
Comments & Troubleshooting Tips
• Sunlight into detector or reflector.
• Re-Align detector.
• Clean detector and reflector.
• Inspect line of sight between detector and
reflector for reflective objects in the pathway.
• Remove blockage.
• Faulty unit.
Remains in alarm until reset or time-out
Remains in fault until reset or time-out
Remains in fault until reset or time-out
Remains in alarm until reset or time-out
I56-3433-004
04-12

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sk-beam-t

Table of Contents