Daikin FXFN71A2VEB Installation And Operation Manual page 22

Indoor unit
Table of Contents

Advertisement

16 Configuration
INFORMATION
▪ The connection of optional accessories to the indoor
unit might cause changes to some field settings. For
more information, see the installation manual of the
optional accessory.
▪ Following setting are only applicable when using the
BRC1H52* user interface. When using any other user
interface, see the installation manual or service manual
of the user interface.
Setting: Ceiling height
This setting must correspond with the actual distance to the floor,
capacity class and air flow directions.
▪ For 3-way and 4-way airflows (which require an optional blocking
pad kit), see the installation manual of the optional blocking pad
kit.
▪ For all-round airflow, use the table below.
If the distance to the floor is (m)
FXFN50
FXFN71, FXFN112
≤2.7
≤3.2
2.7<x≤3.0
3.2<x≤3.6
3.0<x≤3.5
3.6<x≤4.2
Setting: Decoration panel type
When installing or changing the decoration panel type, ALWAYS
check if the correct values are set.
If the ... decoration panel is used
Standard or auto cleaning
Design
Setting: Airflow direction range
This setting must correspond with the needs of the user.
If you want set the airflow direction
range to...
Upper
Medium
Lower
Setting: Air volume when thermostat control is OFF
This setting must correspond with the needs of the user. It
determines the fan speed of the indoor unit during thermostat OFF
condition.
1 If you have set the fan to operate, set the air volume speed:
(1)
Field settings are defined as follows:
• M: Mode number – First number: for group of units – Number between brackets: for individual unit
• SW: Setting number / C1: First code number
• —: Value number / C2: Second code number
: Default
(2)
Fan speed:
• LL: Low fan speed (set during thermostat OFF)
• L: Low fan speed (set by the user interface)
• H: High fan speed
• Setup volume: The fan speed corresponds to the speed the user has set (low, medium, high) using the fan speed button on the user
interface.
• Monitoring 1, 2, 3: The fan is OFF, but runs for a short time every 6 minutes to detect the room temperature by LL (Monitoring 1), by L
(Monitoring 2) or by H (Monitoring 3).
Installation and operation manual
22
During thermostat
OFF at cooling
operation
During thermostat
OFF at heating
operation
(1)
Then
M
SW/C1 —/C2
13 (23)
0
01
02
Setting: Time to clean air filter
03
This setting must correspond with the air contamination in the room.
It determines the interval at which "Time to clean filter" notification
is displayed on the user interface.
(1)
Then
±2500 h (light)
M
SW/C1 —/C2
±1250 h (heavy)
13 (23)
15
01
Notification ON
02
Notification OFF
Setting: Thermostat sensor selection
This setting must correspond with how/if the remote controller
(1)
Then
thermostat sensor is used.
M
SW/C1 —/C2
13 (23)
4
01
02
Used in combination with indoor unit
03
thermistor
Not used (indoor unit thermistor only)
Used exclusively
Setting: Thermostat differential changeover (if remote sensor is
used)
If the system contains a remote sensor, set the increase/decrease
increments.
1°C
0.5°C
If you want...
(2)
LL
Setup volume
(a)
OFF
Monitoring 1
Monitoring 2
Monitoring 3
(2)
H
(2)
LL
Setup volume
(a)
OFF
Monitoring 1
Monitoring 2
Monitoring 3
(2)
H
(a)
Only use in combination with optional remote sensor or when
setting M 10 (20), SW/C1 2, —/C2 3 is used.
If you want an interval of...
(air contamination)
When the remote controller thermostat
sensor is...
If you want to change increments to...
(1)
Then
M
SW/C1 —/C2
12 (22)
6
01
(2)
02
03
(2)
04
(2)
05
(2)
06
07
12 (22)
3
01
(2)
02
03
(2)
04
(2)
05
(2)
06
07
(1)
Then
M
SW/C1 —/C2
10 (20)
0
01
02
3
01
02
(1)
Then
M
SW/C1 —/C2
10 (20)
2
01
02
03
(1)
Then
M
SW/C1 —/C2
12 (22)
2
01
02
FXFN50~112A2VEB
CO₂ Conveni-Pack: indoor unit
3P672850-1B – 2022.01