Display
Parameter [Default]
[P.0]
Remote Start Delay Timing (Input #7) [ 1"]
Range: 1-59 secs or 1-15 mins
Seconds or minutes of continuous REMOTE START command to initiate the automatic engine start
(see section 7.0 and [P20] in this section).
[P.1]
Remote Stop Delay Timing (Input #7) [ 1"]
Range: 1-59 secs or 1-15 mins
Seconds or minutes of continuous absence of the REMOTE START command to initiate the stop cycle
(see section 7.0 and [P.20] in this section).
[P.2]
Crank Timing (Output #10) [ 5"]
Range:1-20 seconds Maximum insertion time of the Starter Motor.
[P.3]
Engine Running Trigger (Input #1) [ 8.0]
Range: 3V-24V, [inh]. If the voltage of the Charger Alternator rises above the [setting], the Starter Motor
is disconnected.
[P.4]
Rest Timing [ 3"]
Range: 3-20 secs. Time interval between starting attempts
[P. 5]
Starting Attempts [ 3 ]
Range: 1-10 This parameter sets the number of attempts in the automatic start cycle
[P.6]
Generator UnderVoltage, short-circuit [ inh.]
Range: 80-400V. If the voltage drops under the [setting] for at least 6 secs, or under [setting]-20% for
1 sec, the Under-Voltage protection [Lo U] will shut down the engine.
[P.7]
Generator Over-Voltage [500V]
Range: 110-550V or [inh.]. If the Generator voltage rises above the [setting] for at least 2 seconds, the
EP6 will energize the over voltage protection [Hi U] (see section 4.0) to stop the engine. The [inh.] code
inhibits the over voltage.
[P.8]
Generator Under-Frequency [Inh.]
[inh.] 1 to 99Hz ([inh]=disables the under frequency)
This protection is delayed by about 6 seconds. The EP6 shuts down the engine and the display will
show the [Lo H] message.
[P.9]
Generator Over-Frequency [55]
45 Hz to [inh.] ([inh.] disables the over frequency)
This protection is delayed by about 2 seconds. The EP6 shuts down the engine and displays [Hi H]
[P.10]
Current Transformer Size [...]
The range is 10/5 up to 1000/5
[P.11]
Generator Overload Setting [inh.]
Range: [inh.] to 1000 AThe EP6 shuts down the engine after a delay of 6 secs and shows the message
[E05].
[P.12]
Generator Failure Alarm [OFF]
selection: [on] or [OFF].The code [on] enables the Generator failure alarm. The EP6 shows the [E04]
message and the engine will shut down.
[P.13]
Glow Plugs/Choke Control (Output #11) [ 5"]
Range: 1 to 99 secs.The EP6 energizes the output #11 for the programmed time.
[P.14]
Output Control [ 0 ]
The following options are available:
[ 0] None - [ 1] Choke Control - [ 2] Glow Plugs Control - [ 3] Choke Control
[P.15]
Belt Break Control [ON]
Selection: [on] or [OFF]. The Belt Break alarm is indicated by means of the message [bELt]
[P.16]
Stop Solenoid Timing [ 2"]
Range: 2-99 secs. Duration of the Stop cycle.
[P.17]
Alarm Output Timing [ 1']
[inh.] 1-59 secs 1-15 mins and [cont]. Time-out of the alarm output. The code [cont] disables the time-out,
and the alarm remains energized until the OFF operating mode is selected. The [inh.] mode enables
the use of the external contactor
[P.18]
Temperature Switch [n.o.]
Selection: [n.o.] or [n.c.]
[n.o.] the engine shuts down if the contact closes
[n.c.] the engine shuts down if the contact opens
[P.19]
ALARM Control [n.c.]
Selection: [n.o.] or [n.c.]
[n.o.] the engine shuts down if the contact closes
[n.c.] the engine shuts down if the contact opens
[P.20]
Remote Start [n.o.]
Selection: [n.o.] or [n.c.]
31
ENGINE PROTECTION