IP RESET Switch

NO APP Switch

USER 1 Switch (LabVIEW Real-Time Module Users)

© National Instruments Corporation
To clear the NI CVS-1450 device IP settings, move the IP RESET switch
to the ON position and reset the NI CVS-1450 device. Use IP RESET
to reset the TCP/IP settings when moving the system from one subnet to
another or when the current TCP/IP settings are invalid.
Resetting the NI CVS-1450 device with the IP RESET switch in the ON
position resets the IP address to
network configuration for the NI CVS-1450 device from a development
machine on the same subnet, or you can use an Ethernet crossover cable to
connect the NI CVS-1450 device directly to the development computer.
To prevent the NI CVS-1450 device from automatically running VIs
at startup, move the NO APP switch to the ON position and reset the
NI CVS-1450 device. If the NI CVS-1450 device becomes inaccessible
because of a startup program, enable the NO APP switch and reset the
NI CVS-1450 device.
The USER 1 switch is user-configurable and has no default functionality.
Use the RT Read Switch VI to read the USER 1 switch state and perform
a custom action based on the current switch state position.
Chapter 2
. You can then set up a new
0.0.0.0
2-5
LEDs, DIP Switches, and Connectors