User Interface For Setup - Veris Industries E51H2 Installation Manual

Bi-directional compact power and energy meter with bacnet ms/tp support
Table of Contents

Advertisement

E51H2, E51H5 Installation Guide
UI for Setup
To: SPASS
S BAC
Back
From:
SETUP > PASWD
Back
S CT
Current
Transformer
Back
S SYS
System
Type
Back
S PT
Potential
Transformer
Back
S
V
Sytem
Voltage
Back
S PWR
Sytem
Voltage
To Setup p. 2 "SPLOS"
ZL0109-0D
Page 16 of 32
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris 'V' logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
KBAUD
--------
MAC
115.2
ID1
--------
76.8
--------
001
38.4
0000
19.2
9.6
CT V
CT SZ
--------
--------
1.0
100
.33
Next
SYSTM
--------
3L-1n
3L
2L-1n
2L
1L+1n
Next
RATIO
--------
001.00
Next
V LL
--------
00600
Next
MX KW
--------
103.92
Next
Note: Bold is the Default.
©2018 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com
Other companies' trademarks are hereby acknowledged to belong to their respective owners.
Set Communications Parameters:
ADDR – BACnet MS/TP MAC Address: 0 – 127.
+ increments the selected (blinking) digit.
ID2
– selects the digit to the left.
--------
BAUD - Baud Rate: 9600 – 115200 Baud
000
BACnet ID: These two screens set the 7 digit
BACnet device ID. Screen ID1 is the most
significant 4 digits and ID2 the least significant
three digits. This is in the range of 0 - 4,194,302.
Next
Set Current Transducer:
CT V - CT Input Voltage: + or – to Select 1.0 or .33V.
CT SZ - CT Size: in Amps. Maximum is 32000 Amps.
Set System Configuration:
SYSTM: + or – to step through the following System Type options:
System
Reg 130 CTs Description
3L-1n
40
3
3L
31
3
2L-1n
12
2
2L
11
1
1L-1n
10
1
Set Potential Transfomer Ratio:
RATIO – Potential transformer step down is RATIO:1. Default is 1:1
(No PT installed). See Install for wiring diagrams. This value must be
set before the System Voltage (if used).
Set System Voltage:
V LL – The nominal Line to Line Voltage for the system. This is used
by the meter to calculate the theoretical maximum system power, and
as the reference voltage for setting the Phase Loss threshold.
Maximum is 32000 Volts. For system type 1+N (10), this is a Line to
Neutral Voltage, indicated by "V LN". Note: the meter will reject settings
that are not within the meter's operating range when divided by the PT
ratio.
System Power:
MX KW – The theoretical Maximum System Power is calculated by the
meter from the System Voltage, CT size, and System Type. Power
Factor is assumed to be unity. The value of System Power is used to
determine which combinations of pulse weight and duration are valid
and will keep up with the maximum power the meter will see. This value
is read only.
Wye Three Phase: A, B, & C with Neutral (Default).
Delta Three Phase: A, B & C; no Neutral
Single Split Phase: A & B with Neutral
Single Phase: A & B; no Neutral
Single Phase: A to Neutral
TM