E51H2, E51H5 Installation Guide
Analog_Input Objects (cont.)
#
Object
Description
Name
AI19
KW_Present_
Total Real Power
Demand
Present Demand
AI20
KVAR_
Total Reactive Power
Present_
Present Demand
Demand
AI21
KVA_Present_
Total Apparent Power
Demand
Present Demand
AI22
KW_Max_
Total Real Power Max
Demand_
Demand Import
Import
AI23
KVAR_Max_
Total Reactive Power
Demand_
Max Demand Import
Import
AI24
KVA_Max_
Total Apparent Power
Demand_
Max Demand Import
Import
AI25
KW_Max_
Total Real Power Max
Demand_
Demand Export
Export
AI26
KVAR_Max_
Total Reactive Power
Demand_
Max Demand Export
Export
AI27
KVA_Max_
Total Apparent Power
Demand_
Max Demand Export
Export
AI28
Reserved_
(Reserved_AI28)
AI28
AI29
E51H2: Pulse
E51H2: Pulse Count
Count
E51H5: Pulse Count 1
E51H5: Pulse_
Count_1
AI30
E51H2:
E51H2: Reserved
Reserved
E51H5: Pulse Count 2
E51H5: Pulse_
Count_2
AI31
KWh_
Real Energy Import
Import_A
Phase A
AI32
KWh_
Real Energy Import
Import_B
Phase B
AI33
KWh_
Real Energy Import
Import_C
Phase C
AI34
KWh_
Real Energy Export
Export_A
Phase A
AI35
KWh_
Real Energy Export
Export_B
Phase B
AI36
KWh_
Real Energy Export
Export_C
Phase C
AI37
KVARh_Q1_A
Reactive Energy Q1
Phase A
AI38
KVARh_Q1_B
Reactive Energy Q1
Phase b
ZL0109-0D
Page 26 of 32
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris 'V' logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
R/W
NV
Units
R
kW
0 - Max_Power (AI76)
R
kVAR
0 - Max_Power (AI76)
R
kVA
0 - Max_Power (AI76)
R
NV
kW
0 - Max_Power (AI76)
R
NV
kVAR
0 - Max_Power (AI76)
R
NV
kVA
0 - Max_Power (AI76)
R
NV
kW
0 - Max_Power (AI76)
R
NV
kVAR
0 - Max_Power (AI76)
R
NV
kVA
0 - Max_Power (AI76)
R
R
0 - 4294967040
R
0 - 4294967040
R
NV
kWh
0 - 3.4+E38
R
NV
kWh
0 - 3.4+E38
R
NV
kWh
0 - 3.4+E38
R
NV
kWh
0 - 3.4+E38
R
NV
kWh
0 - 3.4+E38
R
NV
kWh
0 - 3.4+E38
R
NV
kVARh
0 - 3.4+E38
R
NV
kVARh
0 - 3.4+E38
©2018 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com
Other companies' trademarks are hereby acknowledged to belong to their respective owners.
Range
Returns QNAN or any value
Running count of contact closures on Pulse Input 1 since last reset. Write 16498
(0x4072) to Present_Value of AV1 to reset both pulse counters to 0 (not used
on the E51H5).
E51H2: Reserved
E51H5: Pulse Count 2; Running count of contact closures on Pulse2 input since
last reset. Write 16498 (0x4072) to the Present_Value property of Analog_
Value object AV1 to reset both Pulse Counters to 0.
The Units property of object AI37 reports that these units are kWh because there
is no unit type in the BACnet standard for kVARh
The Units property of object AI38 reports that these units are kWh because there
is no unit type in the BACnet standard for kVARh