To Select Refrigerant Branch Kits; Refrigerant Piping Length And Height Difference - Daikin RXYSQ5TAY1B Installer And User Manual

Hide thumbs Also See for RXYSQ5TAY1B:
Table of Contents

Advertisement

Outdoor unit
Piping outer diameter size (mm)
capacity type (HP)
Gas pipe
Standard
4+5
15.9
6
19.1
B: Piping between refrigerant branch kits
Choose from the following table in accordance with the indoor unit
total capacity type, connected downstream. Do not let the
connection piping exceed the refrigerant piping size chosen by the
general system model name.
Indoor unit capacity
Piping outer diameter size (mm)
index
Gas pipe
<150
150≤x≤182
Example: Downstream capacity for B-1 = capacity index of unit 3-1
+ capacity index of unit 3-2
C: Piping between refrigerant branch kit and
indoor unit
Use the same diameters as the connections (liquid, gas) on the
indoor units. The diameters of the indoor units are as follows:
Indoor unit capacity
Piping outer diameter size (mm)
index
Gas pipe
15~50
63~140
D: Piping between refrigerant branch kit and BP
unit
Total capacity index
Piping outer diameter size (mm)
of connected indoor
Gas pipe
units
15~62
63~149
150~182
5.3.5

Refrigerant piping length and height difference

The piping lengths and height differences must comply with the following requirements. Two patterns will be discussed:
• Outdoor with 100% VRV DX indoor units
• Outdoor with 100% RA DX indoor units
Maximum actual piping length
▪ Example 1.1, unit 8: a+b+c+d+e+f+g+p≤Limit
▪ Example 1.2, unit 6: a+b+h≤Limit
▪ Example 1.2, unit 8: a+i+k≤Limit
▪ Example 1.3, unit 8: a+i≤Limit
▪ Example 2, unit 18: a+b+m≤Limit
Maximum equivalent piping length
Maximum total piping length
▪ Example 1.1: a+b+c+d+e+f+g+h+i+j+k+l+m+n+p≤Limit
▪ Example 2: a+b+c+d+e+f+g+h+i+j+k+l+m≤Limit
Minimum length outdoor-first refrigerant branch kit
▪ Example 2: Limit≤a
RXYSQ4~6TAY1B
VRV IV-S system air conditioner
4P482257-1 – 2017.03
Liquid pipe
Size-up
19.1
9.5
22.2
Liquid pipe
15.9
9.5
19.1
Liquid pipe
12.7
6.4
15.9
9.5
Liquid pipe
12.7
6.4
15.9
9.5
19.1
Requirement
(a)
E: Piping between BP unit and RA DX indoor unit
Indoor unit capacity
Piping outer diameter size (mm)
index
Gas pipe
15~42
50
60
71
5.3.4

To select refrigerant branch kits

For piping example, refer to
"5.3.3  To select the piping size"  on
page 12.
Refnet joint at first branch (counting from outdoor unit)
When using refnet joints at the first branch counted from the outdoor
unit side, choose from the following table in accordance with the
capacity of the outdoor unit. Example: Refnet joint A→B‑1.
Outdoor unit capacity type
(HP)
4~6
Refnet joints at other branches
For refnet joints other than the first branch, select the proper branch
kit model based on the total capacity index of all indoor units
connected after the refrigerant branch. Example: Refnet joint
B‑1→C‑1.
Indoor unit capacity index
<182
Refnet headers
Concerning refnet headers, choose from the following table in
accordance with the total capacity of all the indoor units connected
below the refnet header.
Indoor unit capacity index
<182
INFORMATION
Maximum 8 branches can be connected to a header.
VRV DX
100 m
130 m
300 m
N/A
5 Preparation
Liquid pipe
9.5
6.4
12.7
9.5
15.9
Refrigerant branch kit
KHRQ22M20T
Refrigerant branch kit
KHRQ22M20T
Refrigerant branch kit
KHRQ22M29H
Limit
RA DX
65 m
85 m
140 m
5 m
Installer and user reference guide
13