5 Fix the cable with cable ties to the cable tie mountings.
NOTICE
Make sure to select and install the safety thermostat for the
additional zone according to the applicable legislation.
In any case, to prevent unnecessary tripping of the safety
thermostat, we recommend the following:
▪ The safety thermostat is automatically resettable.
▪ The safety thermostat has a maximum temperature
variation rate of 2°C/min.
▪ There is a minimum distance of 2 m between the safety
thermostat and the 3‑way valve.
INFORMATION
ALWAYS configure the safety thermostat for the additional
zone after it is installed. Without configuration, the indoor
unit will ignore the safety thermostat contact.
6.3.11

To connect a Smart Grid

This topic describes 2 possible ways to connect the indoor unit to a
Smart Grid:
▪ In case of low voltage Smart Grid contacts
▪ In case of high voltage Smart Grid contacts. This requires the
installation of the Smart Grid relay kit (EKRELSG).
The 2 incoming Smart Grid contacts can activate the following Smart
Grid modes:
Smart Grid contact
1
2
0
0
0
1
1
0
1
1
ETVZ16S18+23EA6V+9W
Daikin Altherma 3 H HT F
4P644730-1 – 2021.02
Q4L
13
14
13 14
X5M
Smart Grid operation mode
Free running
Forced off
Recommended on
Forced on
The use of a Smart Grid pulse meter is not mandatory:
If Smart Grid pulse meter is... Then [9.8.8] Limit setting kW
Used
([9.A.2] Electricity meter 2 ≠
None)
Not used
([9.A.2] Electricity meter 2 =
None)
In case of low voltage Smart Grid contacts
Wires (Smart Grid pulse meter): 0.5 mm²
Wires (low voltage Smart Grid contacts): 0.5 mm²
[9.8.4]=3 (Benefit kWh power supply = Smart grid)
[9.8.5] Smart grid operation mode
[9.8.6] Allow electrical heaters
[9.8.7] Enable room buffering
[9.8.8] Limit setting kW
The wiring of the Smart Grid in case of low voltage contacts is as
follows:
X5M
3
4
5
6
9
10
13
14
a
2
1
S4S
S11S
S10S
a
Jumper (factory-mounted). If you also connect a safety
thermostat (Q4L), replace the jumper with the safety
thermostat wires.
S4S
Smart Grid pulse meter
1
Low voltage Smart Grid contact 1
/S10S
2
Low voltage Smart Grid contact 2
/S11S
1 Open the following (see
"4.2.1 To open the indoor
1 Top panel
2 User interface panel
3 Upper switch box cover
2 Connect the wiring as follows:
A
6 Electrical installation
is...
Not applicable
Applicable
unit" [ 4  6]):
1
X5M.4
S4S
X5M.3
X5M.10
S10S
1
X5M.9
X5M.6
2
S11S
X5M.5
Installation manual