Fujitsu AR 18LUAD Series Service Instruction page 79

Duct type inverter, refrigerant r410a, indoor/outdoor unit
Hide thumbs Also See for AR 18LUAD Series:
Table of Contents

Advertisement

Trouble shooting 19
OUTDOOR UNIT Error Method:
Heat Sink Temperature Sensor Error
Detective Actuators:
Outdoor Unit Main PCB Circuit
Heat Sink Temperature Thermistor
Forecast of Cause :
1. Connector connection failure 2.Thermistor failure 3. Main PCB failure
Check Point 1 : Check connection of Connector
Check if connector is removed.
Check erroneous connection.
Check if thermistor cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
OK
OK
Check Point 2 : Remove connector and check Thermistor resistance value
Check Point 2 :
Thermistor Characteristics (Approx. value)
Temperature
Resistance
AR*18L/ 24L
Value (k )
AR*30L/36L/45L/54L
Temperature
Resistance
AR*18L/ 24L
Value (k )
AR*30L/36L/45L/54L
If Thermistor is either open or shorted, replace it and reset the power.
OK
OK
Check Point 3 :
Check Point 3 : Check voltage of Main PCB (DC5.0V)
Make sure circuit diagram of outdoor unit and check terminal voltage at Thermistor (DC5.0V)
1 2
CN21
If the voltage does not appear, replace Main PCB.
Indicate or Display:
Outdoor Unit : LED 8 times blink
ERROR CODE : No indication
Detective details:
When Heat Sink Temperature Thermistor open or short-circuit is
detected at power ON or while running the compressor.
0°C
5°C
10°C
176
135
16.1
12.4
60°C
70°C
80°C
12.5
8.78
1.25
0.89
1 2
1 2
1 2
CN22
CN23
CN26
15°C
20°C
105
81.8
64.5
9.73
7.67
6.10
90°C
100°C
6.31
4.61
3.43
0.65
0.48
0.36
1 2
CN25
07-21
30°C
40°C
50°C
41.1
26.9
18.1
3.95
2.62
1.79
120°C
1.98
0.21