Fujitsu AR 18LUAD Series Service Instruction page 37

Duct type inverter, refrigerant r410a, indoor/outdoor unit
Hide thumbs Also See for AR 18LUAD Series:
Table of Contents

Advertisement

2-2. For AR*30/ 36/ 45LUAN/ AR*45/ 54LUAK
The compressor frequency soon after the start-up is controlled as shown in Figure 9.
(Fig.9 : Compressor Control at Start-up)
Frequency
Hold
Frequency
Time A
(Frequency)
AR*30LUAN
AR*36LUAN
AR*45LUAN
AR*45LUAK
AR*54LUAK
(Time)
AR*30LUAN
AR*36LUAN
AR*45LUAN
AR*45LUAK
AR*54LUAK
1
2
Time B
Time C
Time E
Frequency
Frequency
40Hz
56Hz
56Hz
70Hz
Time A
Time B
180sec
60sec
180sec
80sec
05-09
For AR*30/ 36LUAN
1 Discharge pipe temp. >
2 Discharge pipe temp. < 30°C
For AR*45LUAN / AR*45/ 54LUAK
1 Discharge pipe temp. >
2 Discharge pipe temp. < 35°C
Time C
Time D
120sec
120sec
180sec
180sec
Time D
30°C
=
35°C
=
Time E
720sec
720sec