Rotary
Mounting
System
Rotary
General Rule for
other configura-
tions
c. Aligning the end of the magnet holder flush with the end of the mounting
bracket. Secure the magnet holder with two M4 set screws.
d. Sliding the V-Seal over the magnet holder. You can also check the magnet using
ValVue software by reading sensor counts and comparing them to Table 2.
4. Secure the SVi1000 onto the mounting bracket using four M6 x 20 mm socket
head cap screws.
5. Ensure no interference exists with the position sensor protrusion.
© 2019 Baker Hughes, a GE company, LLC. All rights reserved.
Table 2: Travel Sensor Alignment
Stroke Direction
<60° Rotation
Clockwise or counter-
clockwise rotation
>60° Rotation
Clockwise with increas-
ing setpoint
>60° Rotation
Counter Clockwise rota-
tion with increasing set-
point
Any amount of rotation
Clockwise or counter-
clockwise
Magnet
Orientation
Position
Closed (0%)
(0°)
Full Open
Full Closed
(-45°)
Full Open
Full Closed
(+45°)
50% Travel
(Mid-Stroke)
(0°)
Masoneilan SVi1000 Positioner Quick Start Guide =| 25
Valve
Sensor Counts
0 +/- 1000
-8000 +/- 1500
or
or
+8000 +/- 1500
-8000 +/- 1500
or
or
+8000 +/- 1500
0 +/- 1000