FIGURE 37
MANIFOLD PRESSURE TAP
FIGURE 38
TYPICAL GAS VALVE
INLET
PRESSURE TAP
TABLE 8
LP GAS PIPE CAPACITY TABLE (CU. FT./HR.)
Maximum capacity of pipe in thousands of BTU per hour of undiluted liquefied petroleum gases (at 11 inches water
column inlet pressure).
(Based on a Pressure Drop of 0.5 Inch Water Column)
Nominal
Iron Pipe
Size, Inches
10
20
1/2
275
189
152
3/4
567
393
315
1
1,071
732
590
1-1/4
2,205
1,496
1,212 1,039
1-1/2
3,307
2,299
1,858 1,559
2
6,221
4,331
3,465 2,992
Example (LP): Input BTU requirement of unit, 120,000
Equivalent length of pipe, 60 ft. = 3/4" IPS required.
40
Length of Pipe, Feet
30
40
50
60
70
129
114
103
96
267
237
217
196
504
448
409
378
913
834
771
1,417
1,275
1,181
1,086 1,023
2,646
2,394
2,205
2,047 1,921
MANIFOLD
PRESSURE
TAP
HIGH FIRE
MANIFOLD
PRESSURE
ADJUSTMENT
LOW FIRE
PRESSURE
MANIFOLD
ADJUSTMENT
OUTLET
PRESSURE
TAP
80
90
100
125
150
89
83
78
69
63
182
173
162
146
132
346
322
307
275
252
724
677
630
567
511
976
866
787
1,811 1,606
1,496
Manifold Gas Pressure
Measurement. Natural gas
manifold pressure should be 3.5"
w.c.; LP gas manifold pressure
should be 10" w.c. Only small
variations on gas pressure should be
made by adjusting the pressure
regulator.
1. With the gas shut off at the
manual gas stop, remove the
pressure tap plug in the gas
manifold or the gas valve outlet.
See Figure 37.
2. Connect a U-Tube manometer to
this pressure tap. See Figure 39.
3. Turn on the gas supply and
operate the furnace in high heat
mode.
4. Note or adjust the manifold gas
pressure to give:
A. 3.5" w.c. for natural gas high
fire.
B. 10" w.c. for LP gas high fire.
5. To adjust the pressure regulator
for high fire, remove the regulator
cap located on the side of the
regulator. See Figure 38.
6. Turn the adjustment screw
clockwise to increase pressure or
counterclockwise to decrease
pressure.
7. Securely replace the regulator
cap for high fire.
8. Operate the furnace in low
speed.
9. Note or adjust the manifold
pressure to give:
A. 1.7" w.c. for natural gas low
fire.
B. 4.8" w.c. for LP gas low fire.
10. To adjust the pressure regulator
for low fire, remove the regulator
cap on the top of the regulator.
See Figure 38.
11. Turn the adjustment screw
clockwise to increase pressure or
counterclockwise to decrease
pressure.
12. Securely replace the regulator
cap for low fire.
13. Verify pressures for high and low
fire operation.
14. Shut off gas at the manual gas
valve and remove the U-Tube
manometer.
15. Replace the manifold pressure
tap plug before turning on gas.
Check for leak.