Siemens RUGGEDCOM RX1511 3 Installation Manual page 51

Table of Contents

Advertisement

RUGGEDCOM RX1511
Installation Guide
Test
IEC 61000-4-11
IEC 61000-4-12
IEC 61000-4-16
IEC 61000-4-17
IEC 61000-4-29
IEC 60255-5
a
Siemens-specified severity levels
EMC Immunity Type Tests for IEEE 1613
NOTE
The RUGGEDCOM RX1511 meets Class 2 requirements for an all-fiber configuration and Class 1
requirements for copper ports. Class 1 allows for temporary communication loss, while Class 2 requires
error-free and interrupted communications.
HV Impulse
Dielectric Strength
Fast Transient
EMC and Environmental Type Tests
Description
Voltage Dips and Interrupts
Damped Oscillatory
Mains Frequency Voltage
Ripple on DC Power Supply
Voltage Dips and Interrupts
Dielectric Strength
HV Impulse
Description
Signal ports
DC Power Ports
AC Power Ports
Signal ports
DC Power Ports
AC Power Ports
Signal ports
DC Power Ports
AC Power Ports
AC Power Ports
Signal ports
DC Power Ports
AC Power Ports
Signal ports
DC Power Ports
DC Power Ports
DC Power Ports
Signal ports
DC Power Ports
AC Power Ports
Signal ports
DC Power Ports
AC Power Ports
Test Levels
1000 A/m for 1 s
30% for 1 period
60% for 50 periods
2.5 kV common, 1 kV
differential mode @1 MHz
30 V Continuous
300 V for 1 s
10%
30% for 0.1 s
60% for 0.1 s
100% for 0.05 s
2 kV (Failsafe Relay output)
1.5 kV
2 kV
5 kV (Failsafe Relay output)
5 kV
Test Levels
5 kV (Failsafe Relay Output)
5 kV
2 kV
1.5 kV
2 kV
± 4 kV @ 2.5 kHz
± 4 kV
Chapter 6
Certification
Severity
Levels
5
3
4
3
41

Advertisement

Table of Contents
loading

Table of Contents