Modbus holding registers
A.11 Display settings
MODBUS regis‐
MODBUS ad‐
ter
dress
4:02903
2902
4:02904
2903
4:02907
2906
4:02908
2907
4:02913
2912
4:02914
2913
4:02915
2914
4:02916
2915
Unit settings on MODBUS and the display are linked. Changing the MODBUS units influence the units displayed on the device
1)
and vice versa.
54
No. of bytes Data type
2
Byte
2
Byte
2
Byte
2
Byte
2
Byte
2
Byte
2
Byte
2
Byte
Description
Display line 2:
•
0 = Text for line 3
•
1 = Volumeflow
•
2 = Volumeflow %
•
3 = Q max.
•
4 = Totalizer 1
•
5 = Totalizer 2
•
6 = Batch cycle counter
•
7 = Sensor size
•
8 = Sensor type
•
9 = TAG number
•
10 = Operating time
•
11 = Q max. text
Display line 3:
•
0 = Volumeflow
•
1 = Volumeflow %
•
2 = Q max.
•
3 = Totalizer 1
•
4 = Totalizer 2
•
5 = Batch cycle counter
•
6 = Sensor size
•
7 = Sensor type
•
8 = TAG number
•
9 = Operating time
•
10 = Q max. text
Volumeflow unit
(Page 60)
1)
Volumeflow point
Totalizer 1 unit
1)
(Page 63)
Totalizer 1 point
Totalizer 2 unit
(Page 63)
1)
Totalizer 2 point
Operating Instructions, 03/2021, A5E00753974-AB
Read / write
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
Modbus RTU RS 485