TECHNICAL DATA

TYPE
Thermal power
Pci
Natural gas
(Family 2)
Pressure
Electrical supply
Motor
Capacitor
Ignition transformer
Absorbed electrical power
For gas family 3 (LPG) ask for separate kit.
COUNTRY
GAS CATEGORY
The burner meets protection level of IP X0D (IP 40) as EN 60529.
The burner is approved for intermittent operation as per Directive EN 676.
CE marking according to Gas Appliance Directive 90/396/EEC; PIN 0063AP6680.
According to Directives: Electromagnetic Compatibility 89/336/EEC - 2004/108/EC, Low Voltage
73/23/EEC - 2006/95/EC and Machine 2006/42/EC.
Gas train according to EN 676.
1 – Air damper
2 – Damper fixing screws
3 – Grommet
4 – Hood fixing screw
5 – Air pressure switch
6 – Motor
7 – Lockout lamp with reset button
8 – Control box
9 – 6 pole socket for gas train
10 – Capacitor
NOTES
– The grommet (3) supplied with the burner, must be fitted to the same side of the gas train.
– After having installed the burner verify the access to the fixing screws of the cover.
If necessary, replace them with the fixing screws (4, fig.1) supplied as accessories.
3286
566M
23  58 kW
8  12 kWh/Nm
min. 10 mbar – max. 40 mbar
Single phase, 230 V ± 10%
230 V / 0.65 A (50Hz) – 230 V / 0.45 A (60Hz)
2 F
primary 230 V / 0.2 A
0.15 kW
IT - AT - GR - DK - SE
II2H3B/P
8
9
4
3
20.000  50.000 kcal/h
– 7.000  10.340 kcal/Nm
3
~
GB - IE
NL
II2H3P
II2L3B/P
5
1
GB
ENGLISH
3
50Hz / 60Hz
secondary 8 kV
FR
DE
II2Er3P
II2ELL3B/P
6
10
LU
II2E3B/P
Fig. 1
7
1
2
2
D7386