4.7.1

Firing rate on basis of air density

The firing rate of the burner shown in the manual is valid for a
room temperature of 20°C and an altitude of 0m above sea level
(barometric pressure around 1013 mbar).
It may be that a burner has to operate with combustive air at a
higher temperature and/or higher altitudes.
The heating of the air and the increase in altitude produce the
same effect: the expansion of the air volume (i.e. the reduction of
its density).
The delivery of the burner fan remains essentially the same, but
3
the oxygen per m
of air, and the thrust (discharge head) of the
fan are reduced.
It is therefore important to know if the maximum output requested
from the burner at a determinate combustion chamber pressure
remains within the firing rate of the burner even with the changed
temperature and altitude conditions.
To check it, proceed as follows:
1
find the corrective factor F (relating to the air temperature
and altitude of the system) in the Tab. I.
2
Divide the output Q required from the burner by F to obtain
the equivalent output Qe:
Qe = Q : F (kW)
3
In the firing rate of the burner, mark the work point identified
by:
Qe = equivalent output
H1 = pressure in combustion chamber
point A that must remain within the firing rate.
4
Trace a vertical line from point A)(Fig. 3), and find the maxi-
mum pressure H2 of the firing rate.
5
Multiply H2 by F to obtain the maximum lowered pressure
H3 of the firing rate:
H3 = H2 x F (mbar)
Average baro-
Altitude
metric pressure
m a.s.l.
mbar
0
1013
100
1000
200
989
300
978
400
966
500
955
600
944
700
932
800
921
900
910
1000
898
1200
878
1400
856
1600
836
1800
815
2000
794
2400
755
2800
714
3200
675
3600
635
4000
616
20068428
Technical description of the burner
0
5
10
1.087
1.068
1.049
1.073
1.054
1.035
1.061
1.042
1.024
1.050
1.031
1.013
1.037
1.018
1.000
1.025
1.007
0.989
1.013
0.995
0.977
1.000
0.982
0.965
0.988
0.971
0.954
0.977
0.959
0.942
0.964
0.946
0.930
0.942
0.925
0.909
0.919
0.902
0.886
0.897
0.881
0.866
0.875
0.859
0.844
0.852
0.837
0.822
0.810
0.796
0.782
0.766
0.753
0.739
0.724
0.711
0.699
0.682
0.669
0.657
0.661
0.649
0.638
12
If H3 is greater than H1)(Fig. 3), the burner can produce the de-
livery requested.
If H3 is less than H1, it is necessary to reduce the output of the
burner. The reduction in output is accompanied by a reduction in
the combustion chamber pressure:
Qr
= reduced output
H1r = reduced pressure
Qr
( )
2
H1r = H1 x
Q
Example, 5% reduction in output:
Qr = Q x 0,95
2
H1r = H1 x (0,95)
With the new values - Qr and H1r - repeat steps 2 - 5.
The combustion head should be adjusted in rela-
tion to the equivalent output Qe.
WARNING
mbar
mbar
H2
H3
H1
D388
F
Air temperature °C
15
20
1.031
1.013
1.017
1.000
1.006
0.989
0.995
0.978
0.983
0.966
0.972
0.955
0.960
0.944
0.948
0.932
0.937
0.921
0.926
0.910
0.914
0.898
0.893
0.878
0.871
0.856
0.851
0.836
0.829
0.815
0.808
0.794
0.768
0.755
0.726
0.714
0.687
0.675
0.646
0.635
0.627
0.616
GB
A
Qe
Qe
25
30
0.996
0.980
0.948
0.983
0.967
0.936
0.972
0.956
0.926
0.962
0.946
0.916
0.950
0.934
0.904
0.939
0.923
0.894
0.928
0.913
0.884
0.916
0.901
0.872
0.906
0.891
0.862
0.895
0.880
0.852
0.883
0.868
0.841
0.863
0.849
0.822
0.842
0.828
0.801
0.822
0.808
0.783
0.801
0.788
0.763
0.781
0.768
0.743
0.742
0.730
0.707
0.702
0.690
0.668
0.664
0.653
0.632
0.624
0.614
0.594
0.606
0.596
0.577
kW
kg/h
Fig. 3
40
Tab. I