Thank you for having chosen a product MASE. As a leading generator manufacturer, Mase Generators offers a wide range of generators with an output from 1 KVA portable generators to 1600 KVA units for special applications.
PD 10 S - PD 10.6 S DEFINITIONS USED - The terms used are current technical terms, and where considered necessary the meaning is described below - Generator An assembly of an internal combustion piston engine and an alternate current, synchronous, 2-4 pole, self-excited generator, joined together to create a station for self-production of electrical energy.
Page 5
PD 10 S - PD 10.6 S - Connection in bad state The live parts are not fully covered with insulation removable by destruction only, the connections are not secure because of unstable tightening of the parts and a development of oxide between the parts.
PD 10 S - PD 10.6 S 1 GENERAL INFORMATIONS 1.1 C ONFORM USE The generator is suitable for independent production of electrical energy within the voltage and wattage limits declared by the manufacturer. Any other use outside the already stated field of use is prohibited: the generator is intended for industrial use.
PD 10 S - PD 10.6 S 1.4 P OSITION OF SAFETY LABELS • These labels warn the user of any danger which may cause serious injury. Carefully read the meaning and the precautions described in this manual • If the label detaches or becomes illegible, replace it with a new one which can be requested from an authorised Mase dealer.
Page 9
PD 10 S - PD 10.6 S Obligation Symbols Meaning - Obligation to connect the generator to earth. Prohibition Symbols Meaning - The connections to an emergency electric network must be carried out by specialised electricians in compliance with the relevant regulations in force.
PD 10 S - PD 10.6 S 1.5 G ENERAL DANGER INFORMATIONS • It is recommended to learn how to stop and operate all the controls. • Do not allow unqualified personnel to use the generator. • Even though the generator is protected, do not stand near it.
PD 10 S - PD 10.6 S 1.5.3 D ANGER OF HARM TO HEARING • Do not stand near the generator for long periods without protective earmuffs since hearing may be reduced. Prolonged exposure to noise above 85 dB(A) may cause health disorders. It is in any case recommended to use appropriate protection systems (e.g.
PD 10 S - PD 10.6 S 1.5.7 D ANGER CAUSED BY THE ENGINE STARTING • Do not leave disassembled parts, tools or anything else not forming part of the system on or near the engine. • Install the protections necessary for safety on the parts completing the system.
PD 10 S - PD 10.6 S 1.6 R 1.8 M EFERENCE DOCUMENTS ARKING The instructions for use provided with each generator are The generator identification plate carries all the made up of a collection of documents of which this manual identification data in accordance with the provisions for represents the General Part.
PD 10 S - PD 10.6 S 2 GENERAL CHARACTERISTICS The generators have been designed for use in the industrial field, using highly reliable 3000 rpm air-cooled diesel engines. Particular attention has been paid to the degree of protection against external agents, engine protection...
PD 10 S - PD 10.6 S 2.4 T ABLE OF TECHNICAL CHARACTERISTICS MODEL PD 10 S PD 10/6 S GENERAL FEATURES MAX POWER (LTP) CONTINUOUS POWER (PRP) POWER FACTOR (Cos Φ) THREEPHASE VOLTAGE SINGLEPHASE VOLTAGE RATED FREQUENCY GRADE OF PROTECTION IP 23 MAX TEMP.
PD 10 S - PD 10.6 S 2.5 N OISE EMISSION The values listed are emission levels and not necessarily other sources of noise, such as the number of machines safe operating levels. Although there is a correlation between and other adjacent processes, and the time an operator is emission and exposure levels, this cannot be reliably used exposed to the noise.
PD 10 S - PD 10.6 S 3 INSTALLATION 3.1 G ENERAL INSTALLATION CRITERIA 3.3 E XHAUST PLANT The installation of one or more Generating Sets must be 3.3.1 E XHAUST PIPE designed by specialised engineers qualified for the design of this type of plant. The installation must be...
PD 10 S - PD 10.6 S 3.4 V ENTILATION Do not tamper with the active protections, thermal Ventilation of the room in which the generating set is installed switches and differential magnetothermal switches. is of fundamental importance for the proper operation of the •...
PD 10 S - PD 10.6 S 3.7 O UTDOOR INSTALLATION For units in outdoor installations, it is advisable to ensure a position that provides maximum protection against atmospheric agents, powder, etc. Avoid direct exposure to sunlight that would otherwise cause abnormal heating of the system.
PD 10 S - PD 10.6 S 3.8 I NSIDE INSTALLATION Correct indoor installation of the system must observe the following installation requirements: The site must be adequately dimensioned in order to allow correct operation of the group as well as easy access for routine maintenance operations and eventual repairs.
PD 10 S - PD 10.6 S 4 USING THE GENERATOR 4.1 P RELIMINARY CHECKS - Refuelling must be carried out with the generator Before beginning with any starting procedure, it is off and the key selector in position "0" (STOP) extremely important to become «familiar»...
PD 10 S - PD 10.6 S STOP START 4.4 S TARTING 4.7 E MERGENCY STOP Before starting the generator check that all the utilities are off to prevent putting the still cold engine under For an emergency stop of the generator press the stress.
PD 10 S - PD 10.6 S 5 PROTECTIONS AND WARNING SIGNALS 5.2 F UNCTIONING For the activation, rotate clockwise the key (ref.1) in The generators are equipped with a series of protections position ON. which safeguard it against improper use and faults which Now, rotate the key (ref.1) in position START;...
PD 10 S - PD 10.6 S 6 MAINTENANCE Protect hands from contact with oil by wearing 6.1 P REAMBLE gloves. In the event of accidental contact with engine oil, thoroughly wash the affected part with soap and water. Any maintenance operation on the...
PD 10 S - PD 10.6 S 6.7 B ATTERY CHECK When the operation has been completed, thoroughly The battery only needs to be checked periodically for electrolyte clean off any traces of fuel and dispose of the used level and, if necessary, topped up with distilled water.
PD 10 S - PD 10.6 S 6.9 S 6.10 P CHEDULED MAINTENANCE TABLE ERIOD OF INACTIVITY The check indicated in this section can be carried out either If the generator is not to be used for a long period of time, by the workshop or by machine user.
PD 10 S - PD 10.6 S 7 ANOMALIES, CAUSES AND REMEDIES On starting, the generator does not run and the starter motor does not emit any signal. • Check the battery charge. Recharge the battery. • Check the bloc key. Consult Service Centre.
PD 10 S - PD 10.6 S 8 TRANSPORT, STORAGE, LIFTING AND HANDLING 8.1 T RANSPORT AND STORAGE Packaging: Supplied directly by Mase Generators. The total weight of the packed generator is given in Paragraph 2.4 “Table of technical characteristics”.
PD 10 S - PD 10.6 S 8.3 V ERSION WITH SLOW DRAWN TRAILER A trailer complete with wheels and mobile drawbar is available for movement. The tow is NOT equipped with a parking brake. of shearing: Ensure that the split pin safety catches (ref.4) are in place.
9.1 G UARANTEE • The MASE generators and all their components are guaranteed free of defects and are covered by the guarantee for a period of 2 year from the date of installation. • Not covered by the guarantee are: failed observance of the installation regulations, damage caused by natural...