Schrack Technik GENIO Dual Midi USPRD 1000 VA User Manual

Advertisement

Quick Links

USER MANUAL
UNINTERRUPTIBLE POWER SUPPLY
GENIO Dual Midi
USPRD 1000 – 3000 VA
1 phase input / 1phase output

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the GENIO Dual Midi USPRD 1000 VA and is the answer not in the manual?

Questions and answers

Summary of Contents for Schrack Technik GENIO Dual Midi USPRD 1000 VA

  • Page 1 USER MANUAL UNINTERRUPTIBLE POWER SUPPLY GENIO Dual Midi USPRD 1000 – 3000 VA 1 phase input / 1phase output...
  • Page 2 NTRODUCTION Congratulations on purchasing a GENIO Dual Midi product and welcome to Schrack! To use the support service offered by Schrack, visit the site www.ups-technet.com Our Company is a specialist in the design, development and manufacturing of uninterruptible power supplies (UPS). The UPS described in this manual is a high quality product which has been carefully designed and built in order to guarantee the highest levels of performance.
  • Page 3: Table Of Contents

    ONTENTS PRESENTATION UPS V IEWS RONT VIEW EAR VIEW ISPLAY PANEL VIEW ATTERY ACCESSORY NOT SUPPLIED WITH THE UPS EAR VIEW INSTALLATION NITIAL CONTENT CHECK NSTALLATION ENVIRONMENT ATTERY OX INSTALLATION ETTING THE NOMINAL BATTERY CAPACITY OWER VERSION OWER VERSION WITH BATTERY BOX ACK VERSION ONNECTIONS AND SWITCHING ON FOR THE FIRST TIME WITCHING ON FROM THE MAINS...
  • Page 4 OMMUNICATION ATTERY PACK REPLACEMENT TROUBLESHOOTING LARM CODES AULT TECHNICAL DATA...
  • Page 5: Presentation

    PRESENTATION GENIO Dual Midi uses ON-LINE double conversion technology, resulting in the highest levels of reliability and maximum protection for critical loads such as servers, IT applications and Voice/Data. This family was designed with versatility in mind, allowing for installation in both tower and rack positions. The following shows how the product can be installed in the two different positions: The UPS is also equipped with a dedicated battery pack that allows for easy battery replacement (hot swap) in complete safety thanks to the protected connection system.
  • Page 6: Ups Views

    UPS V IEWS RONT VIEW Extractable/rotatable display plate Removable front panel Release slits Battery pack connector ON/OFF Switch Battery pack retention panel...
  • Page 7: Ear View

    EAR VIEW Model 1000VA / 1500VA Model 2200VA / 3000VA Communication port RS232 Battery expansion connector (optional) USB communication port IEC 10A output socket IEC 16A output socket IEC 16A input plug Communication Card Slots IEC 10A input plug Cooling fans Circuit breaker Remote control terminal board...
  • Page 8: Display Panel View

    ISPLAY PANEL VIEW “SEL” button (Select) Load level indicator “ON” button Configuration area “STAND-BY” button Maintenance request Regular operation Timer Mains operation Measurement display area Battery operation Stand-by / alarm Load powered by bypass EnergyShare Battery charge indicator...
  • Page 9: Battery Box ( Accessory Not Supplied With The Ups )

    ATTERY ACCESSORY NOT SUPPLIED WITH THE UPS The BATTERY BOX is an optional accessory for this range of UPS (same dimensions and aesthetic appearance). The BATTERY BOX contains batteries which allow the operating time of the uninterruptible power supplies to be increased during extended blackouts.
  • Page 10: Installation

    INSTALLATION NITIAL CONTENT CHECK After opening the packaging, it is first necessary to check the contents. The package must contain: Support feet (UK plug?) Schuko power cable - IEC 10A 2 IEC 10A connection cables (IEC 16A only for models 2200/3000VA) USB cable RS232 cable User manual CD + Safety manual...
  • Page 11: Installation Environment

    NSTALLATION ENVIRONMENT The UPS and the Battery Box must be installed in ventilated, clean environments which are sheltered from bad weather. The relative humidity in the environment must not exceed the maximum values shown in the Technical Data table. The ambient temperature, whilst the UPS is in operation, must remain between 0 and 40°C, and the UPS must not be positioned in places which are exposed to direct sunlight or to hot air.
  • Page 12: Tower Version

    OWER VERSION This chapter describes the steps for preparing the UPS and battery box for tower version use. ATTENTION: For your safety and that of the product, you must carefully follow the instructions given here below. BEFORE YOU CARRY OUT THE FOLLOWING SEQUENCE OF OPERATIONS, MAKE SURE THAT THE UPS IS COMPLETELY SWITCHED OFF AND NOT CONNECTED TO THE MAINS POWER SUPPLY OR TO ANY LOAD Once removed from the packaging, the UPS is already preset for installation in the tower configuration.
  • Page 13: Tower Version With Battery Box

    OWER VERSION WITH BATTERY BOX BEFORE CARRING OUT THE FOLLOWING SEQUENCE OF OPERATIONS, ENSURE THAT: • THE UPS IS COMPLETELY SWITCHED OFF AND NOT CONNECTED TO THE MAINS POWER SUPPLY OR TO ANY LOAD. • THE BATTERY BOX IS DISCONNECTED FROM THE UPS, FROM ANY OTHER BATTERY BOXES AND WITH THE BATTERY ISOLATOR OPEN ▪...
  • Page 14: Rack Version

    ACK VERSION The sequence of operations to be followed in order to transform the UPS or battery box into rack version are described below. BEFORE CARRING OUT THE FOLLOWING SEQUENCE OF OPERATIONS, ENSURE THAT: • THE UPS IS COMPLETELY SWITCHED OFF AND NOT CONNECTED TO THE MAINS POWER SUPPLY OR TO ANY LOAD.
  • Page 15: Use

    ONNECTIONS AND SWITCHING ON FOR THE FIRST TIME 1) Check that there is a protection device against overcurrents and short circuits in the system upstream from the UPS. The recommended protection value is 10A (for the 700VA, 1000VA and 1500VA versions) and 16A (for the 2200VA, 3000VA and ER versions) with a B or C trip curve.
  • Page 16: Display Panel Messages

    ISPLAY PANEL MESSAGES This chapter describes, in detail, the various information that can be displayed on the LCD. STATUS MESSAGES ICON STATUS DESCRIPTION Fixed Indicates a fault Flashing The UPS is in stand-by mode Fixed Indicates regular operation Fixed The UPS is operating from the mains The UPS is operating from the mains, but the output voltage is not Flashing synchronised with the mains voltage...
  • Page 17: Measurement Display Area

    EASUREMENT DISPLAY AREA The front panel can be used to display important UPS operating information. When the UPS is switched-on, the display shows the main voltage value. To display a different measurement, press the “SEL” button repeatedly until the desired measurement appears. In the event of a fault/alarm (FAULT) or a lock (LOCK), the display will automatically show the type and code of the corresponding alarm.
  • Page 18: Configuring The Operating Mode

    ONFIGURING THE OPERATING MODE The area of the display shown in the figure displays the active operating mode and allows the user to choose other modes directly from the display panel. HOW TO PROCEED: • To access the configuration area, hold down the “SEL” button for at least 3 seconds. •...
  • Page 19 PROGRAMMABLE AUXILIARY SOCKET (EnergyShare) The EnergyShare sockets are outlets that allow for the automatic disconnection of the load applied to them in certain operating conditions. The events that determine automatic disconnection of the EnergyShare sockets can be selected by the user through the UPStools configuration software. For example, it is possible to select disconnection after a certain period of battery operation;...
  • Page 20: Software

    OFTWARE ONITORING AND CONTROL SOFTWARE The UPSMon software guarantees effective, intuitive UPS management, displaying all the most important information such as input voltage, applied load and battery capacity. It is also able to perform shutdown operations and send e-mails, text messages and network messages automatically when certain events (selected by the user) occur.
  • Page 21: Ups Configuration

    CONFIGURATION The table below illustrates all the possible configurations available to the user in order to best adapt the UPS for individual requirements. It is possible to perform these operations using the UPStools software. FUNCTION DESCRIPTION DEFAULT POSSIBLE CONFIGURATIONS • 50 Hz Selects the nominal output •...
  • Page 22 FUNCTION DESCRIPTION DEFAULT POSSIBLE CONFIGURATIONS • Always connected • Disconnection after no. seconds of battery Select the auxiliary socket Always operation EnergyShare • Disconnection after no. seconds of the battery operating mode connected discharge pre-alarm signal • ... (see UPStools manual) Selects permitted •...
  • Page 23: Communication Ports

    OMMUNICATION PORTS On the back of the UPS (see UPS Views), the following communication ports are present: • RS232 connector • USB connector • Expansion slot for additional communication cards RS232 CONNECTOR RS232 CONNECTOR PIN # SIGNAL NOTES Programmable output *: [default: UPS in lock] (*) Opto-isolated contact max.
  • Page 24: Battery Pack Replacement

    ATTERY PACK REPLACEMENT The UPS is also equipped with a dedicated battery pack that allows for easy replacement of batteries (hot swap) in complete safety, thanks to the protected connection system. • WHEN THE BATTERY PACK IS DISCONNECTED, THE LOADS CONNECTED TO THE UPS ARE NOT PROTECTED IN THE EVENT OF A MAINS FAILURE •...
  • Page 25 Remove the battery pack's retention panel carrying out the operations shown in the figure below. Slip off the battery pack pulling it towards the outside, as shown in the figure below. Be careful when extracting and lifting up the battery pack as it is heavy.. ATTENTION: the new battery pack must contain the same number and type of batteries (see the label located on the battery pack near the connector).
  • Page 26: Troubleshooting

    TROUBLESHOOTING Irregular UPS operation is not always an indication of a fault, and can be due to minor or easy-to-resolve issues It is therefore advisable to consult the table below as it contains information which is useful for solving the most common UPS problems.
  • Page 27 PROBLEM POSSIBLE CAUSE SOLUTION THE BUZZER SOUNDS CONTINUOUSLY AND Reduce the load to within the threshold of 100% (or user THE DISPLAY SHOWS THE LOAD APPLIED TO threshold in the case of code A54). ONE OF THE FOLLOWING THE UPS IS TOO HIGH If the display shows a lock, remove the load and switch CODES: A54, F50, F51, the UPS off and back on again.
  • Page 28: Alarm Codes

    LARM CODES Using a sophisticated self-diagnosis system, the UPS is able to check its own status for any anomalies and/or faults which may occur during normal operation and display them on the display panel. If there is a problem, the UPS signals the event by showing the code and the type of active alarm on the display (FAULT and/or LOCK).
  • Page 29: Lock

    ➢ Active commands: Indicates the presence of an active remote command. CODE DESCRIPTION Remote control 1 (Switch Off) Remote control 2 (load on bypass or manual bypass command) Remote control 3 (Switch On/Off) Battery test in progress LOCK alerts are normally preceded by an alarm signal and their scale leads to the powering-off of the inverter with the load being powered by the bypass line (this procedure is excluded for locks due to serious, persistent overloads and short circuits).
  • Page 30: Technical Data

    TECHNICAL DATA USPRD220/ USPRD300/ UPS MODELS USPRD1000 USPRD1500 USPRD220ER USPRD300ER INPUT Nominal voltage [Vac] 220 - 230 - 240 Maximum operating voltage [Vac] Nominal frequency [Hz] 50 - 60 Rated current (1) 10.5 / 11.5 14 / 15 BATTERY < 4h for 80% of the load Recharge time (standard versions) No.
  • Page 31 BATTERY BOX MODELS JSDH036-NPA- JSDH036-NPM- JSDH072-NPA- JSDH072-NPM- Battery rated voltage [Vdc] 36Vdc 72Vdc Dimensions W x D x H [mm] 87 x 425 x 450 87 x 625 x 450 Weight [Kg] 13.5 20.5 The "-" symbol replaces an alphanumeric code for internal use If the UPS is connected to a battery box, the maximum active power is derated from PF 0.9 to PF 0.8.
  • Page 32 MAN_USPRD100--_EN_2020_0MNSDH1K0RUENUD 0MNSDH1K0RUENUD...