Installation and use manual
UNINTERRUPTIBLE POWER SUPPLY
Series GENIO Tower Plus
USSEP VFI 0,7 - 3kVA
1 phase input / 1 phase output
On Line / Double Conversion (VFI) Technology

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the GENIO Tower Plus USSEP VFI 0,7 and is the answer not in the manual?

Questions and answers

Summary of Contents for Schrack Technik GENIO Tower Plus USSEP VFI 0,7

  • Page 1 Installation and use manual UNINTERRUPTIBLE POWER SUPPLY Series GENIO Tower Plus USSEP VFI 0,7 - 3kVA 1 phase input / 1 phase output On Line / Double Conversion (VFI) Technology...
  • Page 2 NTRODUCTION Congratulations on purchasing a UPS GENIO Tower Plus product and welcome to Schrack! To use the support service offered by Schrack, visit the site www.ups-technet.com The company is highly specialised in the development and production of uninterruptible power supplies (UPSs). The UPSs in this series are high-quality products, carefully designed and manufactured in order to ensure the highest levels of performance.
  • Page 3: Table Of Contents

    ONTENTS PRESENTATION UPS V IEWS RONT VIEW EAR VIEW ISPLAY PANEL VIEW ATTERY ACCESSORY NOT PROVIDED WITH UPS EAR VIEW INSTALLATION NITIAL CONTENT CHECK NSTALLATION ENVIRONMENT ATTERY OX INSTALLATION ETTING THE NOMINAL BATTERY CAPACITY ONNECTIONS AND SWITCHING ON FOR THE FIRST TIME WITCHING ON FROM THE MAINS WITCHING ON FROM THE BATTERY WITCHING OFF THE...
  • Page 4 TROUBLESHOOTING LARM CODES AULT TECHNICAL DATA...
  • Page 5: Presentation

    PRESENTATION GENIO Tower Plus uses ON-LINE double conversion technology, resulting in the highest levels of reliability and maximum protection for critical loads such as servers, IT applications and Voice/Data. It is possible to use one or more autonomy expansion units known as BATTERY BOXES (optional accessories) with the same dimensions and aesthetic line as the UPS alongside it.
  • Page 6: Ups Views

    UPS V IEWS RONT VIEW EAR VIEW 700VA / 1500VA model 1000VA / 1000VA ER model Display Cooling fans Multipurpose buttons Battery expansion connector ON/OFF switch IEC 10A output socket RS232 communication port and contacts IEC 10A input plug USB communication port Remote control terminal board Slot for communication cards...
  • Page 7 2200VA / 2200VA ER / 3000VA / 3000VA ER model RS232 communication port and contacts IEC 16A output socket (only for 3000VA models) USB communication port IEC 10A output socket Slot for communication cards IEC 16A input plug Cooling fans Remote control terminal board Battery expansion connector...
  • Page 8: Display Panel View

    ISPLAY PANEL VIEW “SEL” button (Select) Battery charge indicator “ON” button Load level indicator “STAND-BY” button Configuration area Regulation operation Maintenance request Mains operation Timer Battery operation Measurement display area Load powered by bypass Stand-by / alarm...
  • Page 9: Battery Box ( Accessory Not Provided With Ups )

    ATTERY ACCESSORY NOT PROVIDED WITH UPS The BATTERY BOX is an optional accessory dedicated to this range of UPSs (same dimensions and aesthetic line). The BATTERY BOX contains batteries which allow the operating time of the uninterruptible power supplies to be increased during extended blackouts.
  • Page 10: Installation

    INSTALLATION NITIAL CONTENT CHECK After opening the packaging, it is first necessary to check the contents. The package must contain: Schuko power cable - IEC 10A (for 700AV / 1000VA / 1500VA models); Schuko power cable - IEC 16A (for 2200VA / 3000VA models) IEC 16A male plug IEC 10A connection cable...
  • Page 11: Installation Environment

    NSTALLATION ENVIRONMENT The UPS and the Battery Box must be installed in ventilated, clean environments which are sheltered from bad weather. The relative humidity in the environment must not exceed the maximum values shown in the Technical Data table. The ambient temperature, whilst the UPS is in operation must remain between 0 and 40° C, and the UPS must not be positioned in places which are exposed to direct sunlight or to hot air.
  • Page 12: Use

    ONNECTIONS AND SWITCHING ON FOR THE FIRST TIME 1) Check that there is a protection device against overcurrents and short circuits in the system upstream from the UPS. The recommended protection value is 10A (for the 700VA, 1000VA and 1500VA versions) and 16A (for the 2200VA, 3000VA and ER versions) with a B or C trip curve.
  • Page 13: Display Panel Messages

    ISPLAY PANEL MESSAGES This chapter describes, in detail, the various information that can be displayed on the LCD. STATUS MESSAGES ICON STATUS DESCRIPTION Fixed Indicates a fault Flashing The UPS is in stand-by mode Fixed Indicates regular operation Fixed The UPS is operating from the mains The UPS is operating from the mains, but the output voltage is not Flashing synchronised with the mains voltage...
  • Page 14: Measurement Display Area

    EASUREMENT DISPLAY AREA It is possible to display the most important measurements regarding the UPS in sequence on the display. When the UPS is switched-on, the display shows the main voltage value. To display a different measurement, press the “SEL” button repeatedly until the desired measurement appears. In the event of a fault/alarm (FAULT) or a lock (LOCK), the display will automatically show the type and code of the corresponding alarm.
  • Page 15: Configuring The Operating Mode

    ONFIGURING THE OPERATING MODE The area of the display shown in the figure displays the active operating mode and allows the user to choose other modes directly from the display panel. HOW TO PROCEED: To access the configuration area, hold down the “SEL” button for at least 3 seconds. •...
  • Page 16 REMOTE CONTROL TERMINAL BOARD The remote control terminal allows for implementation of the REPO function (Remote Emergency Power Off) and to remotely switch on/off the UPS. The UPS is provided by the manufacturer with the REPO terminals short-circuited. For installation remove the short circuit and connect to the device's normally closed contact In case of an emergency, if the stop device is used, the REPO control is opened and the UPS goes into stand-by mode and the load is completely disconnected.
  • Page 17: Software

    OFTWARE RS232 ONITORING AND CONTROL SOFTWARE The UPSMon software guarantees effective, intuitive UPS management, displaying all the most important information such as input voltage, applied load, battery capacity. It is also able to perform shutdown operations and send e-mails, text messages and network messages automatically when certain events, selected by the user, occur.
  • Page 18: Ups Configuration

    CONFIGURATION The table below illustrates all the possible configurations available to the user in order to best adapt the UPS to individual requirements. It is possible to perform these operations using the Upstools software. FUNCTION DESCRIPTION DEFAULT POSSIBLE CONFIGURATIONS • 50 Hz Selects the nominal output Output frequency Auto...
  • Page 19 FUNCTION DESCRIPTION DEFAULT POSSIBLE CONFIGURATIONS Selects the permitted Bypass voltage Low: 180V • Low: 180 - 200 in 1V steps voltage range for switching thresholds High: 264V • High: 250 - 264 in 1V steps to the bypass Selects the permitted Bypass voltage Low: 200V...
  • Page 20: Communication Ports

    OMMUNICATION PORTS On the back of the UPS (see UPS Views), the following communication ports are present: RS232 connector • USB connector • Expansion slot for additional communication cards • RS232 CONNECTOR RS232 CONNECTOR PIN # SIGNAL NOTES Programmable output *: [default: UPS in lock] (*) Opto-isolated contact max.
  • Page 21 TROUBLESHOOTING Irregular UPS operation is most likely not an indication of a fault but due to simple problems or distraction. It is therefore advisable to consult the table below carefully as it summarises information which is useful for solving the most common problems.
  • Page 22 PROBLEM POSSIBLE CAUSE SOLUTION THE BUZZER SOUNDS Reduce the load to within the threshold of 100% (or user CONTINUOUSLY AND threshold in the case of code A54). THE DISPLAY SHOWS THE LOAD APPLIED TO If the display shows a lock: ONE OF THE FOLLOWING THE UPS IS TOO HIGH remove the load and switch the UPS off and back on...
  • Page 23 LARM CODES Using a sophisticated self-diagnosis system, the UPS is able to check its own status and any anomalies and/or faults which may occur during normal operation and display them on the display panel. If there is a problem, the UPS signals the event by showing the code and the type of active alarm on the display (FAULT and/or LOCK).
  • Page 24 Active commands: Indicates the presence of an active remote command. CODE DESCRIPTION Remote control 1 (Switch On/Off) Remote control 2 (load on bypass or manual bypass command) Remote control 3 (Switch On/Off) Battery test in progress LOCK alerts are normally preceded by an alarm signal and their scale leads to the power-off of the inverter and the load being powered by the bypass line (this procedure is excluded for locks due to serious, persistent overloads and short circuits).
  • Page 25 TECHNICAL DATA USSEP100 USSEP220 USSEP300 UPS MODELS USSEP70 USSEP150 USSEP100ER USSEP220ER USSEP300ER INPUT Nominal voltage [Vac] 220 - 230 - 240 Maximum operating voltage [Vac] Nominal frequency [Hz] 50 - 60 Nominal current (1) 5 / 5.8 10.5 / 12 14 / 15.5 BATTERY <...
  • Page 26 BATTERY BOX USBB36A3 USBB36M1 USBB72A3 USBB72M1 Nominal battery voltage [Vdc] 36Vdc 72Vdc Dimensions W x D x H [mm] 158 x 422 x 235 190 x 446 x 333 Weight [kg] The “-” symbol replaces an alphanumeric code for internal use.
  • Page 27 MAN_GENIO Tower Plus_0,7-3kVA_EN_2017_03 0MNSEP700RUENUG...