4.7.5 OPEN FLUE APPLIANCE IN A ENCLOSURE VENTILATED DIRECT
TO OUTSIDE AIR
Installations within a compartment ventilated directly to outside air must be ventilated at high and low level.
The minimum free area of permanently open vents must be as follows:-
4.7.6 OPEN FLUE APPLIANCE WITH MECHANICAL VENTILATION
Mechanical ventilation can be a combination of mechanical inlet and outlet and natural ventilation outlet. The
fans must be controlled so as not to cause a negative pressure (relative to atmospheric conditions) in the
plant room. The fans must be interlocked with the appliance. Minimum fl ow rate requirements as as follows:
Minimum fl ow rate with draught
Heater Model
Low level Inlet
MAXXfl o EVO 90
MAXXfl o EVO 120
Installation
Minimum free vent area
Heater Model
MAXXfl o EVO 90
MAXXfl o EVO 120
diverters
High level Extract
360 m
/h
175 m
3
475 m
/h
235 m
3
Low level
High level
1010 cm
590 cm
2
1350 cm
785 cm
2
Minimum fl ow rate without
Low level Inlet
/h
340 m
3
/h
452 m
3
28
2
2
draught diverters
High level Extract
/h
115 m
3
3
/h
155 m
3
3
/h
/h
MAXXfl o EVO