Download Print this page

ABB Relion RER615 DNP3 Communication Protocol Manual page 29

Advertisement

1MRS757820 B
Parameter
Values (Range)
UR offline interval
UR Class 1 Min events
UR Class 1 TO
UR Class 2 Min events
UR Class 2 TO
UR Class 3 Min events
UR Class 3 TO
Legacy master UR
Legacy master SBO
Default Var Obj 01
Default Var Obj 02
Default Var Obj 30
Default Var Obj 32
Recloser Protection and Control RER615
Communication Protocol Manual
Unit
0...65535
min
0...999
0...65535
ms
0...999
0...65535
ms
0...999
0...65535
ms
1=Disable
2=Enable
1=Disable
2=Enable
1...2
1...2
1...4
1...4
Step
Default
1
15
1
2
1
50
1
2
1
50
1
2
1
50
1=Disable
1=Disable
1
1
1
2
1
2
1
4
Section 4
DNP3 parameters
Description
Unsolicited offline interval
Min number of class 1 events to
generate UR
Max holding time for class 1 events to
generate UR
Min number of class 2 events to
generate UR
Max holding time for class 2 events to
generate UR
Min number of class 3 events to
generate UR
Max holding time for class 3 events to
generate UR
Legacy DNP master unsolicited mode
support. When enabled relay does not
send initial unsolicited message.
Legacy DNP Master SBO sequence
number relax enable
1=BI; 2=BI with status.
1=BI event; 2=BI event with time.
1=32 bit AI; 2=16 bit AI; 3=32 bit AI
without flag; 4=16 bit AI without flag.
1=32 bit AI event; 2=16 bit AI event;
3=32 bit AI event with time; 4=16 bit AI
event with time.
23