Download Print this page

ABB Relion RER615 DNP3 Communication Protocol Manual page 23

Advertisement

1MRS757820 B
3.3.3
Recloser Protection and Control RER615
Communication Protocol Manual
Accessing of non-protocol-mapped data
The IED application includes a number of general-purpose I/O data. By default,
these data are mapped to this protocol. See the point list manual for the exact
mappings.
The general-purpose objects can be connected to any internal object in the IED
configuration application using the Application Configuration or Signal Matrix
tool. This gives additional opportunities for the protocols.
Example 1
Due to security reasons, protocols do not contain mappings for the direct control of
physical outputs. This way, the client cannot accidentally write a change to a
physical output.
It is possible to connect general-purpose outputs to physical outputs using the
Application Configuration tool. The general-purpose output can also be controlled
from the protocol.
Example 2
The legacy protocol default mappings are a selection of the most important signals
produced by the IEC 61850-based IED applications. The manufacturer's selection
of important signals may not always serve every customer.
Any non-protocol-mapped internal signal can be freely connected to a general-
purpose input object via the Application Configuration tool. This object can then
be accessed by the legacy protocol as regular protocol application data.
Example 3
The basic IEC 61850 application model of the IED produces a great amount of
information. In some cases, this is more than what is feasible to transport through a
legacy protocol. Via the PCM600/Communication Management tools, unnecessary
data objects can be excluded from the legacy protocol.
However, in some cases a better solution is to OR together several internal signals
into one general signal. This OR output can be connected to a general-purpose
input and accessed by the legacy protocol as regular protocol application data.
Vendor-specific implementation
Section 3
17

Advertisement

loading