Dual Check Backflow Preventer
© Copyright 2023 Caleffi
Product range
3048 Series NPT male, NPT female, press, sweat, PEX crimp, PEX expansion
Technical specifications
Materials
Body, retaining ring and lock nut:
Check valve:
Spring:
O-rings:
Performance
Max. working pressure:
Operating temperature range:
Medium:
Flow rate:
The backflow preventer is ICC-ES certified to ASSE 1024, and complies with NSF/ANSI/CAN 372, low lead laws,
and NSF/ANSI/CAN 61 as certified by ICC-ES. It meets codes IPC, IRC and UPC for use in accordance with the
US and Canadian plumbing codes.
Function
Low lead dual check valve backflow preventer for residential
domestic water supply lines or commercial low-hazard backflow
applications. It prevents reverse flow of unsafe water into main
system water supply. This can occur due to pressure changes in
the distribution network that can force water flow in reverse, or
backwards. The two inline serviceable check valves prevent any
contact between the two systems, closing automatically when
backflow conditions occur. The Caleffi 3048 series is certified to
ASSE 1024 by ICC-ES.
The valve complies with NSF/ANSI/CAN 61 (180°F/82°C Commercial
Hot) as certified by ICC-ES, and complies with NSF/ANSI/CAN 372,
low lead, and codes IPC and UPC or use in accordance with the US
and Canadian plumbing codes, as certified by ICC-ES.
1
www.caleffi.com
3048 Series
pipe sizes 1/2", 3/4", 1"
DZR low-lead brass CW724R-M
EPDM, PPO
stainless steel
peroxide-cured EPDM
160 psi (11 bar)
32 to 180°F (0 to 82°C)
see graph
NA10884
water

Advertisement

loading

Summary of Contents for CALEFFI 3048 Series

  • Page 1 IPC and UPC or use in accordance with the US and Canadian plumbing codes, as certified by ICC-ES. Product range 3048 Series NPT male, NPT female, press, sweat, PEX crimp, PEX expansion pipe sizes 1/2”, 3/4”, 1” Technical specifications...
  • Page 2 CAUTION: Make sure that all the connecting pipework is water tight. Caleffi shall not be liable for damages resulting from stress corrosion, misapplication or misuse of its products.
  • Page 3 Peut ne pas fonctionner correctement et peut mettre en danger l’utilisateur. AVERTISSEMENT: S’assurer que tous les raccordements sont étanches. Caleffi ne pourra etre tenue responsable des dommages resultant de la corrosion, d’une mauvaise utilisation ou une mauvaise utilisation des produits.
  • Page 4 Installation: The Caleffi 3048 series dual check backflow preventer is typically installed downstream of a water meter. A pressure reducing valve (if required) may be installed on either side of the dual check backflow preventer, all subject to local codes and standards.
  • Page 5 Spring check valves Service, maintenance: The Caleffi 3048 should be inspected and cleaned, rebuilt or replaced every 5 years. If excessive pressure drop is experienced in the domestic water supply, dirt or other debris may be causing higher than normal pressure drop in the dual check backflow preventer. The 3048 can be easily inspected by removing the body from the dual union connectors.
  • Page 6 Dimensions: sweat NPT male press* PEX crimp NPT female PEX expansion Code Code (lb/kg) (lb/kg) NPT female threaded connections Press connections* 304843A ⁄ " ⁄ ” ⁄ ” 1.2/0.5 304846A ⁄ " ⁄ ” ⁄ ” 1.0/0.4 304853A ⁄ ” ⁄...
  • Page 7 1/2” 3/4” 1” 10 12.5 15 17.5 20 22.5 25 27.5 30 32.5 35 37.5 7.5 10 12.5 15 17.5 20 22.5 25 27.5 30 32.5 35 37.5 Flow rate, GPM 3048 series 1/2 inch 3/4 inch 1 inch 10.5...
  • Page 8 NOTES Caleffi North America, Inc. 3883 West Milwaukee Road Milwaukee, WI 53208 04-2023 T: 414.238.2360 F: 414.238.2366 For Technical Support call 1-414-338-6338, or email techsupport.us@caleffi.com...