Panasonic S-22MF2E5A8 Service Manual & Test Run Service Manual page 46

Vrf systems indoor unit
Table of Contents

Advertisement

2. Detailed Settings Function
<Procedure of CZ-RTC3 / CZ-RTC5A>
[
]
START
Keep pressing the
1
buttons simultaneously for 4 or more seconds.
The "Maintenance func" screen appears on the
LCD display.
Maintenance func
1. Outdoor unit error data
2. Service contact
3. RC setting mode
4.Test run
Sel.
Press the
2
5
menu.
If you wish to see the next screen instantly, press
the
or
Select "8. Detailed settings" on the LCD display
and press the
Maintenance func
5. Sensor info.
6. Servicing check
7. Simple settings
8. Detailed settings
Sel.
The "Detailed settings" screen appears on the
LCD display.
Select the "Unit no." by pressing the
button for changes.
Detailed settings
Unit no.
3-1
Sel.
20:30 (THU)
Fig. 2-2
,
and
20:30 (THU)
Page [
] Confirm
or
button to see each
button.
button.
20:30 (THU)
Page [
] Confirm
20:30 (THU)
Code no.
Set data
10
0001
Next
Select the "Code no." by pressing the
3
button.
Change the "Code no." by pressing the
button (or keeping it pressed).
Select the "Set data" by pressing the
4
button.
Select one of the "Set data" by pressing the
or
Then press the
5
Select the "Unit no." by pressing the
button and press the
The "Exit detailed settings and restart?" (Detailed
or
setting-end) screen appears on the LCD display.
Select "YES" and press the
5 - 10
VRF SYSTEMS Indoor Unit
Detailed settings
20:30 (THU)
Unit no.
Code no.
Set data
3-1
10
0001
Sel.
Next
button.
button.
Detailed settings
20:30 (THU)
Unit no.
Code no.
Set data
3-1
10
0001
Sel.
[
] Confirm
button.
Detailed settings
20:30 (THU)
Exit detailed settings
Unit no.
Code no.
Set data
and restart?
ALL
01
0002
YES
NO
Sel.
Next
or
or
or
or
button.