Positioning The Rpm Sensor; Opening The Burner; Closing The Burner - Riello 20057519 Installation, Use And Maintenance Instructions

Forced draught gas burners
Table of Contents

Advertisement

7.2.3

Positioning the rpm sensor

In the event the rpm sensor is malfunctioning or
needs replacing, check/reset its position inside
the fan motor cover.
WARNING
To adjust, proceed as follows:
➤ loosen the screws 3) and rest the sensor against the plate of
the disc 2);
➤ referring to the scale 4) draw back the rpm sensor by about
a notch so that there is a distance of about 2 mm from the
disc plate 2).
Key (Fig. 35)
1
Rpm sensor
2
Disc
3
Screw
4
Scale
7.3

Opening the burner

Disconnect the electrical supply from the burner
by means of the main system switch.
DANGER
Close the fuel interception tap.
DANGER
Wait for the components in contact with heat
sources to cool down completely.
➤ Remove the tie-rod 1)(Fig. 36) of the head movement lever,
undoing the nut 2).
➤ Disconnect the socket 4) of the gas servomotor.
➤ Remove the screws 3).
➤ At this point, it is possible to open the burner on the hinge.
7.4

Closing the burner

Refit following the steps described but in reverse order; refit all
burner components as they were originally assembled.
After carrying out maintenance, cleaning or
checking operations, reassemble the hood and all
the safety and protection devices of the burner.
Maintenance
20061128
31
GB
20087860
Fig. 35
Fig. 36
20058392

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rs 1200/ev bluRs 1000/ev blu200575201133 t21134 t2

Table of Contents