Maintenance; Notes On Safety For The Maintenance; Maintenance Programme; Maintenance Frequency - Riello 20057519 Installation, Use And Maintenance Instructions

Forced draught gas burners
Table of Contents

Advertisement

7

Maintenance

7.1

Notes on safety for the maintenance

The periodic maintenance is essential for the good operation,
safety, yield and duration of the burner.
It allows you to reduce consumption and polluting emissions and
to keep the product in a reliable state over time.
The maintenance interventions and the calibration
of the burner must only be carried out by qualified,
authorised personnel, in accordance with the con-
DANGER
tents of this manual and in compliance with the
standards and regulations of current laws.
Before carrying out any maintenance, cleaning or checking oper-
ations:
7.2

Maintenance programme

7.2.1

Maintenance frequency

The gas combustion system should be checked at
least once a year by a representative of the man-
ufacturer or another specialised technician.
7.2.2

Checking and cleaning

The operator must use the required equipment
during maintenance.
Combustion
Carry out an analysis of the combustion discharge gases.
Significant differences with respect to the previous check indicate
the points where more care should be exercised during mainte-
nance.
Combustion head
Open the burner and make sure that all components of the
combustion head are in good condition, not deformed by the
high temperatures, free of impurities from the surroundings
and correctly positioned.
Fan
Check to make sure that no dust has accumulated inside the fan
or on its blades, as this condition will cause a reduction in the air
flow rate and provoke polluting combustion.
Voltage on the QRI cell
Minimum value for correct operation: 3.5V DC (value on AZL dis-
play at about 50%).
If the value is lower, it could be due to:
cell not positioned correctly
low voltage (lower than 187V)
bad regulation of the burner
In order to measure, use a voltmeter with a 10V DC scale con-
nected as in the diagram (Fig. 34).
20058392
Maintenance
Disconnect the electrical supply from the burner
by means of the main system switch.
DANGER
Close the fuel interception tap.
DANGER
Wait for the components in contact with heat
sources to cool down completely.
D9174
Burner
Clean the outside of the burner.
Boiler
Clean the boiler as indicated in its accompanying instructions in
order to maintain all the original combustion characteristics in-
tact, especially the flue gas temperature and combustion cham-
ber pressure.
Gas leaks
Make sure that there are no gas leaks on the pipes between the
gas meter and the burner.
Gas filter
Replace the gas filter when it is dirty.
Combustion
If the combustion values found at the start of the intervention do
not satisfy current standards or anyway indicate a poor state of
combustion (consult the table below), contact the Technical As-
sistance Service for the necessary adjustments.
EN 676
Theoretical
max. CO
GAS
0 % O
G 20
11.7
G 25
11.5
G 30
14.0
G 31
13.7
30
GB
+
Air excess
Max. output
Max. output
λ ≤ 1.2
λ ≤ 1.3
CO
% Calibration
2
2
λ = 1.3
λ = 1.2
2
9.7
9.5
11.6
10.7
11.4
10.5
LMV...
X10-02 / 6
X10-02 / 4
X10-02 / 2
0...10 V
Ri > 10 M
Fig. 34
CO
mg/kWh
≤ 1000
9
≤ 1000
8.8
≤ 1000
≤ 1000
Tab. N