Section 1
Installation and Start-Up

Attach Power Cord

Connect Unit to Electrical

Freezer Start-Up

1-8
Revco ExF
Insert the power cord into the power
inlet module. Place the retaining
bracket (P/N 195763) over the
connector. Tighten retaining screws
to secure.
See the serial tag on the side of the unit for electrical specifications or refer
to the electrical schematics in this manual.
Power
Caution If the factory installed option water cooled condenser is present,
do not turn the freezer on without water connected and flowing. Damage
to the refrigeration system could occur within 5 minutes if water is not
connected and flowing on unit start-up. Refer to Section 5.
The freezer should be operated on a dedicated grounded service. Check the
voltage rating on the serial tag of the unit and compare it with the outlet
voltage. Then, with the power switch turned off, plug the line cord into
the wall outlet.
First, turn on the freezer power switch. Then open the lower front door by
grasping the bottom left corner. Locate the battery switch (Figure 1-5) and
turn it to Standby mode ( ). During initial freezer start-up, the system
battery may require charging and the Low Battery indicator may
illuminate.
Note Ensure the battery switch is turned to Standby mode ( ). The
rechargeable batteries require 36 hours to charge at initial start-up. A "Low
Battery" alarm may occur until the batteries are fully charged. Should a
power failure occur during the initial start-up period, the electronics will
have limited operation.
With the freezer properly installed and connected to power, system set
points can be entered. The following set points can be entered in Settings
mode: Control temperature, high temperature alarm set point, low
temperature alarm set point, and (optional) BUS set point. Default settings
are shown in the table following.
Figure 1-9. Power Cord Connection