5.4.4.2 Setting Communications Parameters (Modbus TCP Protocol)

Context
This section applies to the scenario where the unit is connected to the NMS.
Procedure
Step 1 On the home screen, choose Settings > Comm Settings > WAN IP Settings, and
set the IP address, subnet mask, and gateway based on the actual plan.
Figure 5-7 WAN IP Settings
Step 2 On the home screen, choose Settings > Comm Settings > Modbus Settings.
Parameter
Link mode
Client encryption
Issue 01 (2022-12-30)
NO TE
The WAN IP address cannot be in the 192.168.245.X, 192.168.246.X, or 192.168.248.X
network segment.
Copyright © Huawei Digital Power Technologies Co., Ltd.
Description
● Server: The smart cooling product works as the
server and can connect to two clients for
communication.
● Client: The smart cooling product works as the
client and can connect to a remote server for
communication.
● Server and client: The smart cooling product works
as the server and can connect to two clients for
communication. It also works as the client and can
connect to a remote server for communication.
This parameter is configurable when Link mode
involves Client.
NOTE
In the third-party NMS scenario, if the third-party NMS does
not have a certificate or does not support encryption, you are
advised to set this parameter to Disable for non-encrypted
connection. For security purposes, encryption is enabled by
default. You can configure encryption based on actual
requirements and security scenario evaluation.
5 Power-On Commissioning
96