Warnings; Additional Indications - ABB Relion 650 Series Commissioning Manual

Line distance protection
Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

1MRK 506 336-UEN B
Table 15:
Fault indication
Internal Fault
Real Time Clock Error
Internal Fault
Runtime Exec. Error
Internal Fault
SW Watchdog Error
Internal Fault
Runtime App Error
Internal Fault
File System Error
Internal Fault
TRM-Error
Internal Fault
COM-Error
Internal Fault
PSM-Error
9.2.2

Warnings

The warning message associated with the fault is found in the internal event list in the LHMI
menu Main menu/Diagnostics/Internal events. The message includes the date, time,
description and signal state for the fault. The current status of the internal fault signals can
also be checked via the LHMI in Main menu/Diagnostics/IED status/General.
When a fault appears, record the fault indication message and state it when ordering service.
Table 16:
Warning indication
Warning
IEC 61850 Error
Warning
DNP3 Error
9.2.3

Additional indications

The additional indication messages do not activate internal fault or warning.
The messages are listed in the LHMI menu under the event list. The signal status data is found
under the IED status and in the internal event list.
Line distance protection REL650
Commissioning manual
Internal fault indications
Warning indications
Additional information
IEC 61850 has not
succeeded in some actions
such as reading the
configuration file, startup
etc.
Error in DNP3
communication.
© Copyright 2013 ABB. All rights reserved
Troubleshooting
Additional information
Hardware error with the real time
clock.
One or more of the application
threads are not working properly.
This signal will be activated when
the terminal has been under too
heavy load for at least 5 minutes.
One or more of the application
threads are not in an expected
state.
A file system error has occurred.
A TRM card error has occurred. The
instance number is displayed at the
end of the fault indication.
A COM card error has occurred. The
instance number is displayed at the
end of the fault indication.
A PSM card error has occurred. The
instance number is displayed at the
end of the fault indication.
GUID-7BAFA38E-5163-4E01-A7C3-6489B42233C7 v2
GUID-69561C77-50E8-45E2-B8AC-80116222B5B9 v3.1.1
Section 9
133