2 .4
Installing roof sensors
At this point you must have selected the appropriate spots for the roof sensors and
extended the feeder cable if necessary as prescribed in section 2.3.
The roof sensor may now be installed in connection with the actual construction work
and connected at a later date. The following applies for all types of installations.
a)
The sensor must be placed between or next to the heating
cables, with a distance of minimum 1 cm between sensor
and heating cable.
b)
The sensor must be placed so that the upper brass surface
is horizontal. If the sensor is placed on an angled roof, the
sensor must be levelled until the surface is horizontal.
c)
Fasten the sensor by using the attachments on the sensor
or glue it to the surface.
12
DEVIreg™ 850 ground and roof sensors
min. 1 cm
Installation and user manual