Table Of Advisable Calibrations; Table Of Advisable Calibrations Fgp 50/2 Evo-2 - FBR FGP 50/2 EVO-2 Installation, Use And Maintenance Instructions

Light-oil burners at two stages
Table of Contents

Advertisement

TABLE OF ADVISABLE CALIBRATIONS

TABLE OF ADVISABLE CALIBRATIONS FGP 50/2 EVO-2

Calibrations effected with pressure in chambers 0,1 mbar.
The definitive calibration must be done in operation by means of a combustion analyser.
NOZZLES G.P.H.
II°
60°
45°
2.50
2.50
3.00
3.00
3.50
3.50
4.00
4.50
4.50
5.00
5.00
5.50
5.50
6.00
6.00
6.00
6.00
6.50
6.50
6.50
LEGEND
1) Pressure calibration
2) 2nd stage adjustment
3) 1st stage adjustment
4) Head adjustment
FGP 50/2 EVO-2
START-UP AND CALIBRATION
PRESSURE
FLOW
[bar]
[kg/h]
13
20
12
24
11
28
11
32
11
36
11
40
12
44
12
48
12
50
12
53
Fig. 11
HEAD
AIR OPEN
ADJUSTMENT
1st STAGE
[NOTCH N°]
[NOTCH N°]
1
0.5
1
1
2
2
3
2
4
2
5
2.5
6
3
7
3
8
3
8
3.5
070002_3_B
AIR OPEN
2nd STAGE
[NOTCH N°]
2.5
3.5
4
4.5
5
5
6
7
8
9
11

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents