Mitsubishi Electric PUHZ-SW75VHA.UK Service Manual page 62

Split-type, air to water heat pump
Table of Contents

Advertisement

SW2 setting
Indoor setting temperature
ON
17 – 30
1
2 3 4 5 6
Pressure saturation temperature (T
ON
-39 – 88
1
2 3 4 5 6
Ambient temperature (TH7)
-39 – 88
ON
1
2 3 4 5 6
Outdoor heatsink temperature (TH8)
-40 – 200
ON
1
2 3 4 5 6
Discharge superheat SHd
ON
0 – 255
Cooling = TH4 - T
1
2 3 4 5 6
Heating = TH4 - T
Sub cool. SC
0 – 130
ON
Cooling = T
Heating = T
1
2 3 4 5 6
Input current of outdoor unit
ON
1
2 3 4 5 6
LEV-B opening pulse
ON
1
2 3 4 5 6
U9 error detail history (latest)
ON
1
2 3 4 5 6
OCH533B
Display detail
)
63HS
63HS
63HS
- TH3
63HS
- TH2
63HS
The black square ( ) indicates a switch position.
Explanation for display
17 – 30
-39 – 88
(When the temperature is 0: or less, "–" and
temperature are displayed by turns.)
-39 – 88
(When the temperature is 0: or less, "–" and
temperature are displayed by turns.)
-40 – 200
(When the temperature is 0: or less, "–" and
temperature are displayed by turns.)
(When the thermistor detects 100: or more,
hundreds digit, tens digit and ones digit are
displayed by turns.)
0 – 255
(When the temperature is 100°C or more, hundreds
digit, tens digit and ones digit are displayed by
turns.)
0 – FFFE (in hexadecimal notation)
(When more than FF in hex (255 in decimal), the
number is displayed in order of 16
1
0
16
's and 16
's places.
(Example) When 5000 cycles;
0.5 secs.
0 – 500
(When it is 100 or more, hundreds digit, tens digit
and ones digit are displayed by turns.)
0 – 480
(When it is 100 pulse or more, hundreds digit, tens
digit and ones digit are displayed by turns.)
Description
(No error)
Overvoltage error
Undervoltage error
Input current sensor error
L
-phase open error
1
Abnormal power synchronous signal
PFC error (SW75VHA)
(Overvoltage / Undervoltage / Overcurrent)
PFC/ IGBT error (SW·VHA)
(Undervoltage)
* Display examples for multiple errors:
Overvoltage (01) + Undervoltage (02) = 03
Undervoltage (02) + Power-sync signal error (08) = 0A
L
phase open error (04) + PFC error (10) = 14
1
62
3
's and 16
2
's, and
0.5 secs.
2 secs.
9
C4
Display
00
01
02
04
08
10
20
Unit
:
:
:
:
°C
2 cycles
0.1 A
Pulse
Code
display

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents