Mitsubishi Electric PUHZ-SW75VHA.UK Service Manual page 28

Split-type, air to water heat pump
Table of Contents

Advertisement

Abnormal point and detection method
Error Code
PFC error (Overvoltage/
Detailed
codes
Undervoltage/Overcurrent)
• PFC detected any of the fol-
lowings
a) Increase of DC bus voltage
to 420V.
b) Decrease in PFC control
voltage to 12V DC or lower
10
c) Increase in input current to
50A peak
(SW75VHA only)
U9
PFC/IGBT error (Undervoltage)
• When Compressor is running,
DC bus voltage stays at 310V or
20
lower for consecutive 10 seconds
(SW·VHA only)
Overheat protection
Abnormal if liquid thermistor (TH3), con-
densing temperature T
or more during compressor operation.
Ud
Abnormal pressure of pressure sensor
(63HS)
Abnormal if pressure sensor (63HS)
detects 0.1 MPa or less.
UE
Detection is inoperative for 3 minutes after
compressor starting and 3 minutes after
and during defrosting.
Compressor overcurrent interruption
(When compressor locked)
Abnormal if overcurrent of DC bus or
compressor is detected within 30 seconds
after compressor starts operating.
UF
Current sensor error or input current error
• Abnormal if current sensor detects –1.0A
to 1.0A during compressor operation. (This
error is ignored in case of test run mode.)
UH
• Abnormal if 40A (SW100/120V) of input
current is detected or 37A (SW100/120V)
or more of input current is detected for 10
seconds continuously.
Low pressure (63L operated)
(SW100/120 only)
Abnormal if 63L is operated (under
-0.03MPa) during compressor operation.
63L: Low-pressure switch
UL
OCH533B
1 Abnormal increase in power
source voltage
2 Decrease in power source
voltage, instantaneous stop
3 Disconnection of compressor
wiring
4 Misconnection of reactor (ACL)
5 Defective outdoor power circuit
board
6 Defective reactor (ACL)
7 Disconnection or loose
connection of CN2 on the
outdoor power circuit board/
controller circuit board
1 Incorrect switch settings on the
outdoor controller circuit board
for model select
2 Defective outdoor power circuit
board
3 Defective outdoor controller circuit
board
1 Defective outdoor fan (fan
motor) or short cycle of outdoor
detects 70:
unit during cooling operation
63HS
2 Defective liquid thermistor
(TH3), condensing temperature
T
63HS
3 Defective outdoor controller board
1 Disconnection or contact
failure of connector (63HS) on
the outdoor controller circuit
board
2 Defective pressure sensor
3 Defective outdoor controller
circuit board
1 Stop valve is closed.
2 Decrease of power supply
voltage
3 Looseness, disconnection or
converse of compressor wiring
connection
4 Defective compressor
5 Defective outdoor power board
1 Disconnection of compressor
wiring
2 Defective circuit of current
sensor on outdoor power circuit
board
3 Decrease of power supply
voltage
1 Stop valve of outdoor unit is
closed during operation.
2 Disconnection or loose
connection of connector (63L)
on outdoor controller board
3 Disconnection or loose
connection of 63L
4 Defective outdoor controller
board
5 Leakage or shortage of
refrigerant
6 Malfunction of linear expansion
valve
Case
12 Check the field facility for the power
supply.
3 Correct the wiring (U . V . W phase) to
compressor. Refer to 11-7 (Outdoor power
circuit board).
4 Correct the wiring of reactor (ACL).
5 Replace outdoor power circuit board.
6 Replace reactor (ACL).
7 Check CN2 wiring.
1 Correction of a model select
2 Replace outdoor power circuit board.
3 Replace outdoor controller circuit board.
1 Check outdoor unit air passage.
23 Turn the power off and on again to check
the error code. If U4 is displayed, follow
the U4 processing direction.
1 Check connection of connector (63HS) on
the outdoor controller circuit board.
Check breaking of the lead wire for
thermistor (63HS).
2 Check pressure by microprocessor.
(Pressure sensor/ 63HS)
(SW2: Refer to 11-8.)
3 Replace outdoor controller board.
1 Open stop valve.
2 Check facility of power supply.
3 Correct the wiring (U
compressor.
Refer to 11-7 (Outdoor power circuit board).
4 Check compressor.
Refer to 11-5.
5 Replace outdoor power circuit board.
1 Correct the wiring (U
compressor. Refer to 11-7 (Outdoor power
circuit board).
2 Replace outdoor power circuit board.
3 Check the facility of power supply.
1 Check stop valve.
2~4 Turn the power off and on again to check
if F3 is displayed on restarting.
If F3 is displayed, follow the F3 processing
direction.
5 Correct to proper amount of refrigerant.
6 Check linear expansion valve.
Refer to 11-5.
28
Judgment and action
V
W phase) to
V
W phase) to

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents