Code Description
EA1
Load safeties
Safeties
EA2
alarm
compressor/fan input
EA3
activation.
EA4
NOTE: with step
EA6
compressors 1 input
for each compressor
has to be used.
C1-LA Minimum
Suction pressure or
pressure
temperature lower
(temperature)
than
alarm
LAL value
compressors
section
F-LA Minimum
Condensing pressure
pressure
or temperature lower
(temperature)
than
alarm fans
LAF value
section
C1-HA Maximum
Suction pressure or
pressure
temperature higher
(temperature)
than
alarm
HAL value
compressors
section
F-HA Maximum
Condensing pressure
pressure
or temperature higher
(temperature)
than
alarm fans
HAF value
section
A5
Liquid level
Input enabled
alarm
A12
Configuration
See par. 18.1
alarms
A14
Load
A load has worked for
maintenance
the hour set in the
alarm
SEr parameter
dtL
Discharge
Pb3 Temperature
Line
Higher than dtL
Temperature
for the dLd time
delay
InF
Inverter fan
The configurable
alarm
dig. Input set as
inF is activated
FC01
Running
The digital input
...
proof alarm
set as Co1.. Co6
FC04
with
has
automatic
activated by d1d,
recover
... d4d time
LC01
Running
5 running proof
...
proof alarm
alarms happened
LC06
with manual
in a hour.
recover
1592001440 XC645CX GB r3.4 31.10.2017.docx
Cause
Action
the
corresponding
load is turned
off. (with step
compressors all
relays referred
to the input are
disabled).
signaling only
signaling only
signaling only
Depends on the
parameter HFC
signaling only
- signaling only
Digital Scroll
switched off
The analog out
set as INF is
switched off
The compressor
1..4 is switched
not
been
off and the safety
timers start
The compressor
1..4 is switched
off
Reset
Recovery depends on ALMr parameter:
With ALMr = no The instrument restart the
standard operating mode when the input is
disabled.
With ALMr = yES manual recover for the alarms
of compressors and fans. Push the DOWN key for
3s.
Automatically: as soon as the pressure or
temperature reaches the (LAL+ differential) value.
(differential = 0.3bar or 1°C)
Automatically: as soon as the pressure or
temperature reaches the (LAF+ differential) value.
(differential = 0.3bar or 1°C)
Automatically: as soon as the pressure or
temperature reaches the (HAL - differential) value.
(differential = 0.3bar or 1°C)
Automatically: as soon as the pressure or
temperature reaches the (HAF - differential)
value.
(differential = 0.3bar or 1°C)
Automatically as soon as the input is disabled
Manually: reset the running hour of the
compressor
(see par.13 Running hours of loads)
Automatically as soon as the temperature
becomes lower than dtL.
Automatically as soon as the input is disabled
Automatic – when safety timers are over
Manual by means:
Controller off-on
-
Reset by keyboard
-
Reset by monitoring system
-
XC645CX