PURONR (R- -410A) QUICK REFERENCE GUIDE

Puron refrigerant operates at 50- -70 percent higher pressures than R- -22. Be sure that servicing equipment and replacement
S
components are designed to operate with Puron refrigerant.
Puron refrigerant cylinders are rose colored.
S
Recovery cylinder service pressure rating must be 400 psig, DOT 4BA400 or DOT BW400.
S
Puron refrigerant systems should be charged with liquid refrigerant. Use a commercial type metering device in the manifold hose
S
when charging into suction line with compressor operating
Manifold sets should be 700 psig high side and 180 psig low side with 550 psig low- -side retard.
S
Use hoses with 700 psig service pressure rating.
S
Leak detectors should be designed to detect HFC refrigerant.
S
Puron refrigerant, as with other HFCs, is only compatible with POE oils.
S
Vacuum pumps will not remove moisture from oil.
S
Do not use liquid- -line filter driers with rated working pressures less than 600 psig.
S
Do not leave Puron refrigerant suction line filter driers in line longer than 72 hours.
S
Do not install a suction- -line filter drier in liquid line.
S
POE oils absorb moisture rapidly. Do not expose oil to atmosphere.
S
POE oils may cause damage to certain plastics and roofing materials.
S
Wrap all filter driers and service valves with wet cloth when brazing.
S
A factory approved liquid- -line filter drier is required on every unit.
S
Do NOT use an R- -22 TXV.
S
If indoor unit is equipped with a R- -22 TXV or piston metering device, it must be changed to a hard- -shutoff Puron refrigerant
S
TXV.
Never open system to atmosphere while it is under a vacuum.
S
When system must be opened for service, recover refrigerant, evacuate then break vacuum with dry nitrogen and replace filter
S
driers. Evacuate to 500 microns prior to recharging.
Do not vent Puron refrigerant into the atmosphere.
S
Do not use capillary tube coils.
S
Observe all warnings, cautions, and bold text.
S
All indoor coils must be installed with a hard- -shutoff Puron refrigerant TXV metering device.
S
Copyright 2009 CAC / BDP D 7310 W. Morris St. D Indianapolis, IN 46231
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
Printed in U.S.A.
Edition Date: 07/09
12
Catalog No: IM---FX4D---01
Replaces: NEW