Toshiba VN-M1500HE Installation Manual page 16

Air to air heat exchanger
Table of Contents

Advertisement

Air to Air Heat Exchanger
Central control system (When controlling the Air to Air Heat Exchanger only)
D
For the settings of the central control address, refer to the Installation Manual of the central control device.
Power supply
Central controller
L N
U1
U2
U3
U4
Central control wiring
Air to Air Heat
Air to Air Heat
Exchanger
Exchanger
U1
U2
U1
A B
L N
U3
U4
L N
U3
Power
Power
supply
supply
Remote controller
Remote controller
A B
(header)
(follower)
Remote controller
inter-unit wiring
* Central control wiring must be connected to the header Air to Air Heat Exchanger unit only.
* For group control, install inter-unit wiring between the units.
* Up to 8 units can be installed for group control.
Changing the group address (No.4 of SW703)
Settings for changing the group address are necessary. Select "Header: ON" on the header unit of each group
which central control wiring is connected to. Select "Follower" for the other units.
* Settings of the header unit reflect the indications of the remote controller. (Factory default: Follower)
Changing the indoor unit address (No.1 to 4 of SW702, No.1 and 2 of SW703)
Settings for changing the indoor unit address are necessary. Do not duplicate the value. (1 to 64)
* The header unit does not need to be selected as "1". (Factory default: 1)
Changing the terminator (No.1 of SW301)
Settings for changing the terminator are necessary. Select "ON" for one of the header unit.
(Factory default: OFF)
100 Ω: ON (1 header unit only)
None: OFF (the other units)
29-EN
Installation Manual
Air to Air Heat
Air to Air Heat
Exchanger
Exchanger
U2
U1
U2
A B
A B
U4
L N
U3
U4
L N
Power
Power
supply
supply
Remote controller
Remote controller
A B
A B
(header)
(follower)
Remote controller
inter-unit wiring
Changing the
terminator
100 Ω: ON
None: OFF
(Factory default: OFF)
Air to Air Heat Exchanger
– 15 –
Central control system (When controlling the air conditioner and the Air to Air Heat Exchanger
E
separately)
For the settings of the central control address, refer to the Installation Manual of the central control device.
Power supply
L1 L2 L3 N
U1 U2 U3 U4 U5 U6
Control wiring
between indoor and
outdoor units
U1
U2
A B
U3
U4
Indoor unit
U1 U2
L N
Power
A B
supply
Remote controller
(header)
* Central control wiring of the Air to Air Heat Exchanger is necessary only for the header unit.
* For group control, install inter-unit wiring between the units.
* Up to 8 units can be installed for group control.
Changing the group address (No.4 of SW703)
Settings for changing the group address are necessary. Select "Header: ON" on the header unit of each group
which central control wiring is connected to. Select "Follower" for the other units.
* When "Header: ON" is selected, "Individual: ON" will be selected if only one Air to Air Heat Exchanger is
connected to this system.
SW301
* Settings of the header unit reflect the indications of the remote controller. (Factory default: Follower)
ON
ON
Changing the indoor unit address (No.1 to 4 of SW702, No.1 and 2 of SW703)
OFF
Settings for changing the indoor unit address are necessary. Do not duplicate the value. (1 to 64)
1
2
* The header unit does not need to be selected as "1". (Factory default: 1)
Changing the terminator (No.1 of SW301)
* The settings do not need to be adjusted.
Power supply
Outdoor unit
Central controller
L N
U1
U2
Central
U3
U4
control
wiring
Control wiring between
Central control wiring
indoor units
Air to Air Heat
Indoor unit
Exchanger
A B
U1 U2
A B
L N
L N
Power
Power
supply
supply
Remote controller
Remote controller
A B
A B
(follower)
(header)
Remote controller
inter-unit wiring
Installation Manual
Air to Air Heat
Exchanger
U1
U2
U1
U2
A B
A B
U3
U4
L N
U3
U4
Power
supply
Remote controller
A B
A B
(follower)
Remote controller
inter-unit wiring
30-EN