Toshiba VN-M1500HE Installation Manual page 13

Air to air heat exchanger
Table of Contents

Advertisement

Air to Air Heat Exchanger
System example
D
Central control system
(When controlling the Air to Air Heat Exchanger only)
Central controller for 64/128 units / groups
(TCB-SC642TLE2, BMS-CM1280TLE)
U3 U4
U3 U4
U3 U4
Air to Air
Air to Air
Air to Air
Heat
Heat
Heat
Exchanger
Exchanger
Exchanger
A B
A B
A B
A B
A B
A B
Remote controller for the Air to Air Heat Exchanger
(NRC-01HE)
Remote controller for air conditioner (RBC-AMS41E)
Central control system
E
(When controlling the air conditioner and the Air to Air Heat
Exchanger separately)
Central controller for 64/128
Outdoor
units / groups
unit
(TCB-SC642TLE2, BMS-
CM1280TLE)
U1 U2
U3 U4
U3 U4
U1 U2
U1 U2
U3 U4
Air
Air
Air to Air
conditioner
conditioner
Heat
Exchanger
A B
A B
A B
A B
A B
A B
Remote controller for the
Remote controller for the Air to Air
air conditioner
Heat Exchanger (NRC-01HE)
(RBC-AMT32E, RBC-
AMS41E)
Remote controller for air conditioner
(RBC-AMS41E)
F
Central control system
(When controlling the air conditioner and Air to Air Heat
Exchanger together)
Central controller for 64/128
Outdoor
unit
units / groups
(TCB-SC642TLE2
BMS-CM1280TLE)
U1 U2
U3 U4
U3 U4
U1 U2
U1 U2
Air
Air
Air to Air
conditioner
conditioner
Heat
Exchanger
A B
A B
A B
Remote controller for air
conditioner
A B
(RBC-AMT32E, RBC-AMS41E)
Remote controller for the Air to Air
Heat Exchanger (NRC-01HE)
23-EN
Installation Manual
Operation
• The central controller can be used to ON/OFF the whole
system and separately ON/OFF groups of the Air to Air
Heat Exchangers.
• The central controller cannot be used to control the
ventilation fan speed or ventilation mode of the Air to Air
Heat Exchanger.
• If the central controller and the remote controller for the Air
to Air Heat Exchanger are used, the latter operation
overrides the former.
Air to Air
• The remote controller for the Air to Air Heat Exchanger
Heat
(NRC-01HE) can be used to control the ventilation fan
Exchanger
speed and ventilation mode of the Air to Air Heat
Exchanger.
A B
* The remote controllers for the air conditioners (RBC-
A B
AMT32E) cannot be used to control the group of the Air
to Air Heat Exchangers. Only on/off operation is
available for RBC-AMS41E.
• The central controller can be used to ON/OFF the whole
system and separately ON/OFF groups of air conditioners
and the Air to Air Heat Exchangers. (Air conditioners and
Air to Air Heat Exchangers are not linked in this system.)
• The central controller cannot be used to control the
ventilation fan speed or ventilation mode of the Air to Air
Heat Exchanger.
• The operation of the central controller overrides that of the
remote controllers for the Air to Air Heat Exchangers and
the air conditioners. However, the operation of the remote
controller for the Air to Air Heat Exchanger does not affect
that of the remote controller for the air conditioner and vice
Air to Air
Heat
versa.
Exchanger
• The remote controller for the Air to Air Heat Exchanger
(NRC-01HE) can be used to control the group of the air
A B
conditioners instead of using the remote controller for the
air conditioner.
A B
• The remote controller for the Air to Air Heat Exchanger
(NRC-01HE) can be used to control the ventilation fan
speed and ventilation mode of the group of the Air to Air
Heat Exchangers.
* The remote controllers for the air conditioners (RBC-
AMT32E) cannot be used to control the group of the Air
to Air Heat Exchangers. Only on/off operation is
available for RBC-AMS41E.
• The central controller can be used to ON/OFF the whole
system. It can also be used to ON/OFF the Air to Air Heat
Exchanger separately (*).
• The central controller cannot be used to control the
ventilation fan speed or ventilation mode of the Air to Air
Heat Exchanger.
• If three control devices are used; the central controller and
the remote controllers for the Air to Air Heat Exchanger and
the air conditioner, the latter operation overrides the former
regardless of which device is used.
• The remote controller for the Air to Air Heat Exchanger
Air to Air
NRC-01HE can be used to control the ventilation fan speed
Heat
Exchanger
and ventilation mode of the Air to Air Heat Exchanger.
• If the remote controller for the air conditioner (RBC-
A B
AMT32E and RBC-AMS41E) is used; the ventilation fan
speed or ventilation mode of the Air to Air Heat Exchanger
can not be controlled.
A B
• The remote controller for the air conditioner or the Air to Air
Heat Exchanger can be used to ON/OFF the Air to Air Heat
Exchanger separately.
* Setting modifications are required for separate control.
Refer to "11. Advanced control" on page 19.
Air to Air Heat Exchanger
Air to Air Heat Exchanger system
System example
A
Central control
No. of Air to Air Heat
1
Exchangers
Operation together with the air
conditioners
Remote controller inter-unit
Not necessary
wiring
Central control wiring
1.Line (system) address Fixed
* The line (system) address is fixed as 31 for the Air to Air Heat Exchanger.
2.Changing the indoor
Not necessary
unit address
Factory default: 1
No.1 to 4 of SW702
No.1 and 2 of SW703
3.Changing the group
Necessary
address
Header (Individual):
No.4 of SW703
ON
4.Fix / Automatic
changeover of the
central control
address
No.3 of SW703
5.Changing the
terminator
No.1 of SW301
Checking before turning on
Complete the settings of the Air to Air Heat
the power
Exchanger and wiring.
Turning on the power
Turn on the breaker of all the Air to Air Heat
Exchangers.
Central control address
setting
– 12 –
Installation Manual
Air to Air Heat Exchanger system linked
with air conditioners
B
None
Multiple
1
No
Yes
Necessary
Not necessary
Necessary
Not necessary
Necessary
No duplication
Factory default: 1
No duplication
Factory default: 1
Factory default: 1
Necessary
Not necessary
Header: ON (1unit)
Follower: OFF (all units)
Follower: OFF (the
* Settings of the follower unit with the smallest
other units)
indoor unit address number reflect the
indication of the remote controller.
* Settings of the
header unit reflect
the indications of
the remote
controller.
Not necessary
Not necessary
None: OFF
• Complete the settings of the Air to Air Heat
Exchanger and wiring.
• Refer to the Installation Manual of the air
conditioner for the settings and wiring.
Turn on the Air to Air Heat Exchanger first.
Refer to the Installation Manual of the air
conditioner for its power supply.
Not necessary
C
Multiple
EN
24-EN

Advertisement