Set Temperature Rise - Bryant G Series Installation & Operating Instructions Manual

Upflow gas-fired induced-combustion furnaces
Table of Contents

Advertisement

TABLE 7—GAS RATE CU FT/HR
SIZE OF
SECONDS
TEST DIAL
FOR 1
1
2
REVOLUTION
cu ft
cu ft
10
360
720
11
327
655
12
300
600
13
277
555
14
257
514
15
240
480
16
225
450
17
212
424
18
200
400
19
189
379
20
180
360
21
171
343
22
164
327
23
157
313
24
150
300
25
144
288
26
138
277
27
133
267
28
129
257
29
124
248
30
120
240
31
116
232
32
113
225
33
109
218
34
106
212
35
103
206
36
100
200
37
97
195
38
95
189
39
92
185
40
90
180
41
88
176
42
86
172
43
84
167
44
82
164
45
80
160
46
78
157
47
76
153
48
75
150
49
73
147
(3.) When correct input is obtained, replace regulator
seal cap. Main burner flame should be clear blue,
almost transparent. (See Fig. 13.)
INLET
PRESSURE TAP
Fig. 12—Redundant Automatic Gas Control Valve
d. High altitude—In the United States gas input on rating
plate is for altitudes up to 2000 ft. Ratings for altitudes
over 2000 ft must be 4 percent less for each 1000 ft
above sea level. To obtain the adjusted altitude rating,
adjust the manifold pressure (see item c) and replace the
main burner orifices as needed. Refer to National Fuel
Gas Code Appendix F, Table F-4 for proper orifice
sizing at high altitudes.
SIZE OF
SECONDS
TEST DIAL
FOR 1
5
1
2
REVOLUTION
cu ft
cu ft
cu ft
1800
50
72
144
1636
51
71
141
1500
52
69
138
1385
53
68
136
1286
54
67
133
1200
55
65
131
1125
56
64
129
1059
57
63
126
100
58
62
124
947
59
61
122
900
60
60
120
857
62
58
116
818
64
56
112
783
66
54
109
750
68
53
106
720
70
51
103
692
72
50
100
667
74
48
97
643
76
47
95
621
78
46
92
600
80
45
90
581
82
44
88
563
84
43
86
545
86
42
84
529
88
41
82
514
90
40
80
500
92
39
78
486
94
38
76
474
96
38
75
462
98
37
74
450
100
36
72
439
102
35
71
429
104
35
69
419
106
34
68
409
108
33
67
400
110
33
65
391
112
32
64
383
116
31
62
375
120
30
60
367
ON AND
OFF SWITCH
GAS
PRESSURE
REGULATOR
ADJUSTMENT
MANIFOLD
PRESSURE TAP
5
cu ft
360
355
346
340
333
327
321
316
310
305
300
290
281
273
265
257
250
243
237
231
225
e. Canadian installations only—The Canadian ratings are
220
approved for altitudes up to 2000 ft for natural and
214
propane gases. High-altitude ratings are from 2000 ft to
209
205
4500 ft above sea level. See Table 8 for nominal burner
200
orifice size. High-altitude rating includes a 10 percent
196
192
derate as required by Canadian standards.
188
184
180
178
GAS
173
170
Natural
167
Propane
164
161
155

2. Set temperature rise.

150
Furnace must operate within range of temperature rise
specified on the unit rating plate. Determine the air tem-
perature rise as follows.
a. Place duct thermometers in return and supply ducts as
near furnace as possible. Be sure thermometers do not
"see" heat exchangers so that radiant heat will not affect
thermometer readings. This is particularly important
with straight-run ducts.
b. When thermometer readings stabilize, subtract return-air
temperature from supply-air temperature to determine
temperature rise.
c. Adjust air temperature rise by adjusting blower speed.
Increase blower speed to reduce temperature rise. De-
crease blower speed to increase temperature rise.
WARNING: Disconnect the electrical power before
changing the speed tap. A failure to follow this warning
can cause personal injury.
d. To change blower motor speed selections for heating
mode, remove blower motor lead from control board
HEAT terminal. (See Fig. 11.) Select desired blower
A95618
motor speed lead from 1 of the other terminals and
relocate it to HEAT terminal. See Table 9 for lead color
identification. Reconnect original lead on SPARE termi-
nal.
CAUTION: Recheck temperature rise. It must be within
limits specified on unit rating plate. Recommended op-
eration is at midpoint of rise or above.
—13—
BURNER FLAME
MANIFOLD
Fig. 13—Burner Flame
TABLE 8—CANADIAN ORIFICE SIZE
SEA LEVEL
0—2000 FT
43
54
BURNER
A89020
HIGH ALTITUDE
2000—4500 FT
44
55

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

395cav

Table of Contents