EXAMPLE: (0—2000 ft altitude)
Furnace rating plate input is 110,000 Btuh.
Btu heating input = Btu/cu ft X cu ft/hr
Heating value of gas = 1050 Btu/cu ft
Time for 1 revolution of 2-cu ft dial = 70 sec
Gas rate = 103 cu ft/hr (from Table 8)
Btu heating input = 1050 X 103 = 108,150 Btuh
In this example, the orifice size and manifold pressure
adjustment is within ±2 percent of the furnace input rate.
TABLE 8—GAS RATE (CU FT/HR)
SIZE OF
SECONDS
TEST DIAL
FOR 1
1
2
5
REVOLUTION
cu ft
cu ft
cu ft
10
360
720
1800
11
327
655
1636
12
300
600
1500
13
277
555
1385
14
257
514
1286
15
240
480
1200
16
225
450
1125
17
212
424
1059
18
200
400
100
19
189
379
947
20
180
360
900
21
171
343
857
22
164
327
818
23
157
313
783
24
150
300
750
25
144
288
720
26
138
277
692
27
133
267
667
28
129
257
643
29
124
248
621
30
120
240
600
31
116
232
581
32
113
225
563
33
109
218
545
34
106
212
529
35
103
206
514
36
100
200
500
37
97
195
486
38
95
189
474
39
92
185
462
40
90
180
450
41
88
176
439
42
86
172
429
43
84
167
419
44
82
164
409
45
80
160
400
46
78
157
391
47
76
153
383
48
75
150
375
49
73
147
367

2. Set temperature rise.

Furnace must operate within range of temperature rise
specified on the furnace rating plate. Determine the air
temperature rise as follows.
a. Place duct thermometers in return and supply ducts as
near furnace as possible. Be sure supply-air thermom-
eters do not "see" heat exchangers so that radiant heat
will not affect thermometer readings. This is particularly
important with straight-run ducts.
b. When thermometer readings stabilize, subtract return-air
temperature from supply-air temperature to determine
temperature rise.
c. Adjust air temperature rise by adjusting blower speed.
Increase blower speed to reduce temperature rise. De-
crease blower speed to increase temperature rise.
SIZE OF
SECONDS
TEST DIAL
FOR 1
1
2
5
REVOLUTION
cu ft
cu ft
cu ft
50
72
144
360
51
71
141
355
52
69
138
346
53
68
136
340
54
67
133
333
55
65
131
327
56
64
129
321
57
63
126
316
58
62
124
310
59
61
122
305
60
60
120
300
62
58
116
290
64
56
112
281
66
54
109
273
68
53
106
265
70
51
103
257
72
50
100
250
74
48
97
243
76
47
95
237
78
46
92
231
80
45
90
225
82
44
88
220
84
43
86
214
86
42
84
209
88
41
82
205
90
40
80
200
92
39
78
196
94
38
76
192
96
38
75
188
98
37
74
184
100
36
72
180
102
35
71
178
104
35
69
173
106
34
68
170
108
33
67
167
110
33
65
164
112
32
64
161
116
31
62
155
120
30
60
150
INLET
PRESSURE TAP
Fig. 13—Redundant Automatic Gas Control Valve
BURNER FLAME
MANIFOLD
WARNING: Disconnect the electrical power before
changing the blower motor speed tap. A failure to follow
this warning can cause personal injury.
d. To change blower motor speed selections for heating
mode, remove blower motor lead from control HEAT
terminal. (See Fig. 10.) Select desired blower motor
speed lead from 1 of the other terminals and relocate it
to HEAT terminal. See Table 9 for lead color identifi-
cation. Reconnect unused lead on SPARE terminal.
→TABLE 9—SPEED SELECTOR
COLOR
Black
Yellow (When
present)
Blue
Red
White
—16—
ON AND
OFF SWITCH
MANIFOLD
PRESSURE TAP
BURNER
Fig. 14—Burner Flame
FACTORY-
SPEED
ATTACHED TO
High
Medium-High
Medium-Low
Low
Common
L2/COM
GAS
PRESSURE
REGULATOR
ADJUSTMENT
A95618
A89020
Cool
Spare
Heat
Spare

Advertisement

Table of Contents
loading

Table of Contents