Mosa RENTAL Use And Maintenance Manual page 30

Table of Contents

Advertisement

LAMP NAME
Yellow warning lamp
This alarm is activated when ECU send information that ECU Yellow lamp is activated. LBO ALARM is not activated, after
deactivation of lamp, alarm automatically disappears.
This output is active when the ECU sends an active "yellow lamp" flag, i.e. it has detected a non-critical malfunction.
This flag is taken from the DM1 frame on standard J1939 ECUs. Some ECUs provide this flag in their own proprietary fra-
mes and some do not provide the flag at all.
Red stop lamp
This alarm is activated when ECU send information that ECU Red lamp is activated. LBO ALARM is not activated, after
deactivation of lamp, alarm automatically disappears.
This output is active when the ECU sends an active "red lamp" flag, i.e. it has detected a critical malfunction and the engine
should not be operated until a service check is performed. This flag is taken from the DM1 frame on standard J1939 ECUs.
Some ECUs provide this flag in their own proprietary frames and some do not provide the flag at all.
Engine wait to start
lamp
This alarm is activated when ECU send information that ECU Wait To Start lamp is activated. LBO ALARM is not activated,
after deactivation of lamp, alarm automatically disappears.
This output is active when ECU Wait To Start Lamp is active.
ATT filter lamp
This alarm is activated when ECU send information that ECU ATT Filter Lamp is activated. LBO ALARM is not activated,
after deactivation of lamp, alarm automatically disappears.
This output is active when ATT Filter Lamp is active.
Exhaust system high
temperature lamp
This alarm is activated when ECU send information that ECU ATT Hest Lamp is activated. LBO ALARM is not activated,
after deactivation of lamp, alarm automatically disappears.
This output is closed if ECU send signal HEST Lamp. If ECU stop send HEST LAMP signal binary input will be opened
without no matter if alarms in alarmlist are confirmed or not.
SCR error lamp
This alarm is activated when ECU send information that ECU ATT SCR Error Lamp is activated. LBO ALARM is not activa-
ted, after deactivation of lamp, alarm automatically disappears.
This output is active when ATT SCR Error Lamp is active.
DEF low level lamp
This alarm is activated when ECU send information that ECU ATT DEF Level Lamp is activated. LBO ALARM is not activa-
ted, after deactivation of lamp, alarm automatically disappears.
This output is active when ATT DEF Level Lamp is active.
Regeneration inhibit
lamp
This alarm is activated when ECU send information that ECU ATT Inhibited Lamp is activated. LBO ALARM is not activated,
after deactivation of lamp, alarm automatically disappears.
This output is active when ATT Inhibited Lamp is active.
ACTIVE ICON
INACTIVE ICON
ATS - AFTER TREATMENT SYSTEM
ALARM
AHI ECU Yellow lamp
ECU YELLOW LAMP
AHI ECU Red lamp
ECU RED LAMP
AHI ECU Wait to start
ECU WAIT TO START
AHI ATT Filter Lamp
ATT FILTER LAMP
AHI ATT HEST Lamp
ATT HEST LAMP
AHI ATT SCR Error
ATT SCR ERROR
Lamp
LAMP
AHI ATT DEF Level
ATT DEF LEVEL
Lamp
LAMP
AHI ATT Inhibited
ATT INHIBITED LAMP
Lamp
KOHLER
OUTPUT (LBO)