Starting And Stopping; Controls; Controls Description - Mosa RENTAL Use And Maintenance Manual

Table of Contents

Advertisement

Pos.
Description
AB
Generator control unit IL4-
AMF9
B6
Controller power switch
L7
Forced Regeneration Button
L8
Inhibition Regeneration
Button
L5
Emergency stop button
R3
Siren
B7
Service switch
Z2
Thermal-magnetic circuit
breaker
T5
Earth leakage relay
Only for UE version
A3
Insulation monitoring
Only for DGUV version
F
Fuse
Q3
Output power terminals
12
Earth terminal
D5
Auxiliary terminal block
15
A.C. socket
D
Ground Fault Interrupter
Only for DGUV version
N2
G.F.I. and circuit breaker
Function
Control board of the genset.
Starting and stopping the generator.
Generator alarm management.
Display of: alarms, measurements, operational messages.
Controller power on/off switch.
Starts the PDF forced regeneration process
It inhibits the PDF forced regeneration process
To be pushed in case of danger. Immediate stop of the gen-set.
Gen-set acoustic alarm.
Switch reserved for service
ATTENTION if closed with the engine running, it prevents the engine from
stopping
"General switch for the gen-set.
It protects both gen-set and related electrical circuit from over current /
short circuit."
Protection device against indirect contact for TN systems (GE neutral to
ground). It opens the general circuit breaker, thereby interrupting the power
supply to the electrical system. The generator stop.
The regulations on the GFI must be performed by qualified personnel.
Protection device against indirect contact for IT systems (GE neutral not to
ground).
It opens the general circuit breaker when the isolation resistance falls
below the selected threshold, thereby interrupting the power supply to the
electrical system.
The regulations on the RCM must be performed by qualified personnel.
Auxiliary circuits protection
Terminal output for load connection.
Ground connection point for gen-set.
Connection of signals and auxiliary controls
AUX sockets for load connection.
GFI 300mA – B type for 400V / 63A socket
Protection of loads connected to a.c. power sockets
30 mA - Type A for EU version - Type B for DGUV version

CONTROLS DESCRIPTION