Eaton xDetect Large Panel Installation And Operation Manual

Eaton xDetect Large Panel Installation And Operation Manual

Fire panel system
Table of Contents

Advertisement

Quick Links

xDetect Fire Panel System
Installation and operation manual

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the xDetect Large Panel and is the answer not in the manual?

Questions and answers

Summary of Contents for Eaton xDetect Large Panel

  • Page 1 xDetect Fire Panel System Installation and operation manual...
  • Page 2: Table Of Contents

    12.1 Commissioning the system using the HMI ......50 InStallatIon anD oPeratIon manual 25-15049-G October 2021 www.eaton.com...
  • Page 3 12.8 Configuring Cause and Effect ........77 InStallatIon anD oPeratIon manual 25-15049-G October 2021 www.eaton.com...
  • Page 4 12.12.3 Factory reset ..........86 InStallatIon anD oPeratIon manual 25-15049-G October 2021 www.eaton.com...
  • Page 5 22 . SuPPorteD lanGuaGeS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 122 InStallatIon anD oPeratIon manual 25-15049-G October 2021 www.eaton.com...
  • Page 6: Document Update Notes

    IF BatterY IS rePlaCeD BY an InCorreCt tYPe DISPoSe oF tHe uSeD BatterIeS aCCorDInG to tHe InStruCtIonS this product must only be disposed of in accordance with the Weee directive . InStallatIon anD oPeratIon manual 25-15049-G October 2021 www.eaton.com...
  • Page 7: List Of Abbreviations

    Up to 250 panels can be networked together to form a single system capable of operating up to 200,000* devices. *(200 devices x 4 loop cards) x 250 networked panels = 200,000 devices InStallatIon anD oPeratIon manual 25-15049-G October 2021 www.eaton.com...
  • Page 8: Functions Relating To Bs En54

    The total alarm load across each conventional type sounder output = 0.75 A Outputs can be wired in loop or spur configurations. If wired as a spur then an EOL device (200 Ω + Diode) must be fitted for correct operation (Eaton part no. EOLCF3VDS).
  • Page 9 (option 7 .10 BS en54-2) This output, which is fused, and monitored using an end of line device (Eaton part no. EOLCF3VDS) used for the transmission of the fire signals to controls for automatic fire protecting equipment (e.g. Door released units etc). It operates by providing 24 V output to an auxiliary device ( e.g.
  • Page 10 - Found on Gateway card (14-0417) (option 8 .9 BS en54-2) This output, which is fused and monitored using 6K8 end of line resistor (Eaton part no. 01-3370), is used for the transmission of fault signals to fault warning routing equipment.
  • Page 11: Optional Functions

    The detectors are checked continuously for 30 seconds. If after this time, the detector is still in alarm, the output will be activated otherwise the detector will be reset. InStallatIon anD oPeratIon manual 25-15049-G October 2021 www.eaton.com...
  • Page 12: Ancillary Functions

    Although the panel can supply a continuous quiescent load of up to 30 mA, BS 5839-1 precludes this practice and any ancillary equipment you connect should only consume power in the alarm or fault mode to meet the requirement of BS 5839-1. InStallatIon anD oPeratIon manual 25-15049-G October 2021 www.eaton.com...
  • Page 13: Technical Specifications

    Mains Voltage Nominal 230 Vac +10%, -15% 50/60Hz 230 Vac +10%, -15% 50/60Hz Mains Current Maximum (@195 V) Output (VB1) Voltage 20.4-28.1 V 20.4-28.1 V Current Maximum Output (VB2) Voltage 20.4-28 V Current Maximum InStallatIon anD oPeratIon manual 25-15049-G October 2021 www.eaton.com...
  • Page 14 Input Current maximum 60 mA Output Current maximum 55 mA 250 mA Fuse (resettable PTC) 100 mA 2.5 A 100 mA 250 mA Cable length maximum 2 km 2 km 2 km 2 km InStallatIon anD oPeratIon manual 25-15049-G October 2021 www.eaton.com...
  • Page 15: Compatible Equipment

    RoLP) up to 262 Maximum Fire alarm (2 loop panel) devices per CIE up to 524 (4 loop panel) 5. Compatible Equipment For a list of compatible devices please see www.eaton.com/xDetect InStallatIon anD oPeratIon manual 25-15049-G October 2021 www.eaton.com...
  • Page 16: Overview - Xdetect - All Variants

    230 Vac +10%, -15% 50/60Hz Security Lockable door Memory Micro SD Card Batteries 4 x 12 V, 12 Ah SLA battery. Yuasa NP12-12 (Recommended). 2 x 12 V, 12 Ah SLA battery. Yuasa NP12-12 (Recommended). InStallatIon anD oPeratIon manual 25-15049-G October 2021 www.eaton.com...
  • Page 17: Installation

    Temperatures in excess of 40°C and below -5°C should be avoided, if in doubt consult Eaton. The panel should be located away from any potential hazard, in a position where it is readily accessible to authorised staff, and the fire services, ideally on the perimeter of a building near a permanent entrance.
  • Page 18: Mounting Instructions

    Small panel - 4 x 20mm diameter (2 per side) c. Rear: W:284 x H:35mm d. Base: 2 x 20mm diameter ote: Do not remove more knockouts than required. Use appropriate cable glands. InStallatIon anD oPeratIon manual 25-15049-G October 2021 www.eaton.com...
  • Page 19 35.5mm 121.2mm 421mm 124.7mm Figure 3 . Front view of xDetect large Panel back box with door not attached Wire the unit. For details refer to ‘Wiring Details’ section on page 22 WarnInG ISolate PoWer DurInG InStallatIon InStallatIon anD oPeratIon manual 25-15049-G October 2021 www.eaton.com...
  • Page 20 Small master panel Mounting Holes 350mm 31.5mm 121.6mm 415mm 125mm Mounting Holes Figure 5 . Front view of xDetect Small Panel back box with door not attached WarnInG ISolate PoWer DurInG InStallatIon InStallatIon anD oPeratIon manual 25-15049-G October 2021 www.eaton.com...
  • Page 21 7. Installation xDetect master panels - Door measurements 22.7mm 433mm Figure 6 . xDetect large master panel door 22.7mm 426.4mm Figure 7 . xDetect Small master panel door InStallatIon anD oPeratIon manual 25-15049-G October 2021 www.eaton.com...
  • Page 22: Wiring Details

    7.2.1 PSU to Battery - Large Panel Variants xDetect Large panel variants fitted with a single PSU require 2 x 12 V @ 12 Ah sealed lead acid batteries to provide backup power in event of mains failure. Insert batteries in panel after wall mounting.
  • Page 23 7. Installation xDetect Large panel variants fitted with a Dual PSU require 4 x 12 V @ 12 Ah sealed lead acid batteries to provide backup power in event of mains failure. Insert batteries in panel after wall mounting. For information on adding an additional PSU,...
  • Page 24 . Black Figure 10 . xDetect large Panel battery connection diagram Figure 11 . For tidiness, we recommend securing the battery connection wiring using the provided battery straps...
  • Page 25 . Black Black Figure 12 . xDetect large Panel battery connection diagram Figure 13 . For tidiness, we recommend securing the battery connection wiring using the provided battery straps InStallatIon anD oPeratIon manual 25-15049-G October 2021 www.eaton.com...
  • Page 26: Psu To Battery - Small Panel Variants

    Insert batteries in panel after wall mounting. Insert the batteries as follows: Figure 14 . Battery insertion order . Secure the batteries using the provided battery straps InStallatIon anD oPeratIon manual 25-15049-G October 2021 www.eaton.com...
  • Page 27 . Black Figure 15 . xDetect Small Panel battery connection diagram Figure 16 . For tidiness, we recommend securing the battery connection wiring using the provided battery straps InStallatIon anD oPeratIon manual 25-15049-G October 2021 www.eaton.com...
  • Page 28: Card Wiring And Connections

    1 in the Auto learn routine). Terminals 1 + 2 is the loop Finish and should be connected to the last device of the loop. Figure 17 . xDetect loop Card 1l Protocol 800 wiring connections InStallatIon anD oPeratIon manual 25-15049-G October 2021 www.eaton.com...
  • Page 29 3 + 4 at the other) or as a spur, using terminals 1 + 4. The spur configuration requires an external 200R + Diode EOL (Eaton part no. EOLCF3VDS, provided with the panel) at the end of the spur.
  • Page 30 IN port, and vice versa. AUX OUT Figure 20 . xDetect network Card wiring connections NETWORK CARD NETWORK CARD NETWORK CARD PANEL 1 PANEL 2 PANEL 3 Figure 21 . xDetect network Card loop wiring example InStallatIon anD oPeratIon manual 25-15049-G October 2021 www.eaton.com...
  • Page 31 PSE2 LIVE NEUTRAL RIGHT EARTH BATTERY LEFT BATTERY Not currently DOOR TAMPER used JUMPER FOR EARTH SWITCH FAULT MONITORING – PANEL I/D JUMPERS Figure 23 . xDetect PSe Backplane Board wiring connections InStallatIon anD oPeratIon manual 25-15049-G October 2021 www.eaton.com...
  • Page 32 Figure 24 . xDetect large Card - earthing, HmI and Card connection points Earth points HMI connection Card sockets Figure 25 . xDetect Small Card - earthing, HmI and Card connection points InStallatIon anD oPeratIon manual 25-15049-G October 2021 www.eaton.com...
  • Page 33 Figure 26 . xDetect large example wiring for Gateway and loop card FP200 type cable (2.5mm max.) Suitable cable glands should be used Figure 27 . xDetect Small example wiring for Gateway and loop card InStallatIon anD oPeratIon manual 25-15049-G October 2021 www.eaton.com...
  • Page 34 Figure 29 . attaching the data and ground cables 4. Security: When the panel is installed in public area please lock the door to prevent unauthorized tampering. Authorized users should be provided with key as required. InStallatIon anD oPeratIon manual 25-15049-G October 2021 www.eaton.com...
  • Page 35 Figure 31 . attaching the data and ground cables 4. Security: When the panel is installed in public area please lock the door to prevent unauthorized tampering. Authorized users should be provided with key as required. InStallatIon anD oPeratIon manual 25-15049-G October 2021 www.eaton.com...
  • Page 36 . Figure 33 . example wiring for PSu . earth wire must be grounded at nearby earthing point, then routed through the ferrite with one turn of wire . InStallatIon anD oPeratIon manual 25-15049-G October 2021 www.eaton.com...
  • Page 37 3. Using the supplied bolts, firmly attach the bracket first to the front of the power supply, then to the stud on the backbox. Figure 35 . xDetect large Variant - securing additional PSu . InStallatIon anD oPeratIon manual 25-15049-G October 2021 www.eaton.com...
  • Page 38 . Figure 37 . example wiring for PSu . earth wire must be grounded at nearby earthing point, then routed through the ferrite with one turn of wire . InStallatIon anD oPeratIon manual 25-15049-G October 2021 www.eaton.com...
  • Page 39 The above also applies to any distributed power supply (i.e. mains connections for control panels, relay units etc.). Cable segregation All cables for the fire alarm system should be segregated from any other cables/ wiring/services. InStallatIon anD oPeratIon manual 25-15049-G October 2021 www.eaton.com...
  • Page 40: Networking

    Continuous earth connections across a large network should be avoided. ote: If a networked panel is hard reset, it is recommended to perform a hard reset on all panels on the network to align current event data. InStallatIon anD oPeratIon manual 25-15049-G October 2021 www.eaton.com...
  • Page 41: Panel Controls & System Status Indicators

    Emitted flashing when 1 or more local FPE faults is active. Delays Active Amber Emitted when 1 or more delays are active on the local system. Optional 2 Amber Not used. HMI (Touch Screen Display) Zonal Indicators (128ZI / 256ZI panels only) InStallatIon anD oPeratIon manual 25-15049-G October 2021 www.eaton.com...
  • Page 42: Hmi Overview

    10. System Status Indicators 28. Silence buzzer/Mute buzzer’ (not interactive) Action Button 11. Panel Name 29. Change Language Action Button 12. Login Button 30. Display LED Icon Legend 13. View Fires Button InStallatIon anD oPeratIon manual 25-15049-G October 2021 www.eaton.com...
  • Page 43: Basic User Interface Functionality

    If a status indicator LED is illuminated, you can quickly check it’s function and • description at any time by pressing the ‘Display leD Icon legend Button’. The legend will auto dismiss after 10 seconds. InStallatIon anD oPeratIon manual 25-15049-G October 2021 www.eaton.com...
  • Page 44: First Time Start Up

    An SD card with appropriate image and language data must be inserted into the HMI SD card holder. To begin installation, press ‘Install Panel’. INSTALL PANEL Image data will be installed first, followed by language data. UPDATING IMAGES UPDATING LANGUAGES InStallatIon anD oPeratIon manual 25-15049-G October 2021 www.eaton.com...
  • Page 45 System Initialising System Details Installer Details Name: Email: Phone: Last Commissioned: 05/08/2021 Last Serviced: Loops: 0 HMI Language Pack: 6.7 PSU Count: 2 Log Entries: 35 Network Size: N/A Touch to continue... InStallatIon anD oPeratIon manual 25-15049-G October 2021 www.eaton.com...
  • Page 46: Language Selection

    Polish Quiescent Screen Once your language has been selected, you will be taken to the quiescent screen. (The logo is changeable by the user) xDetect 23/8/21 19:09 Panel 2 Alarm Count: 0 InStallatIon anD oPeratIon manual 25-15049-G October 2021 www.eaton.com...
  • Page 47: Logging In And Selecting A User

    After 5 minutes of inactivity, the user will be automatically logged out and returned to the home screen. 5. Once successfully logged in, return to the menu screen by pressing the ‘menu action Button’ InStallatIon anD oPeratIon manual 25-15049-G October 2021 www.eaton.com...
  • Page 48: Set Time & Daylight Saving

    Day light saving can be enabled by ticking the checkbox ‘DSt adjust?’ on left side. xDetect 23/8/21 19:09 Panel 2 Alarm Count: 0 Set Time 19 : DST Adjust? InStallatIon anD oPeratIon manual 25-15049-G October 2021 www.eaton.com...
  • Page 49: Set Date

    Date can be adjusted by pressing or holding the arrow buttons. Date can be confirmed and set by pressing the tick box. xDetect 23/8/21 19:09 Panel 2 Alarm Count: 0 Set Date 2021 InStallatIon anD oPeratIon manual 25-15049-G October 2021 www.eaton.com...
  • Page 50: Commissioning

    Tests Computer Commissioning 2. Select ‘auto-learn’ xDetect 23/8/21 19:09 Panel 2 Alarm Count: 0 Auto-Learn Loop Devices Input Zones Output Groups Panel Programmable Sounder Loop Status LED Comfort Locate Device Circuits Mode InStallatIon anD oPeratIon manual 25-15049-G October 2021 www.eaton.com...
  • Page 51 (or check enable/Disable all). xDetect 23/8/21 19:09 Panel 2 Alarm Count: 0 Full Auto Learn - Select Loop(s) Confirm Full Auto Learn Select/Clear All Press ‘Confirm Full auto learn’ to continue. InStallatIon anD oPeratIon manual 25-15049-G October 2021 www.eaton.com...
  • Page 52 . Instead, use the ‘adding/Insert/Delete/Clear Devices’ functions in xDetectWorks software (see page 76) . InStallatIon anD oPeratIon manual 25-15049-G October 2021 www.eaton.com...
  • Page 53: Comfort Mode

    Event Log Settings Tests Computer Commissioning 2. Select ‘leD Comfort mode’ from the commissioning menu. xDetect 23/8/21 19:09 Panel 2 Alarm Count: 0 Auto-Learn Rapid Faults Loop Status LED Comfort Locate Device Mode InStallatIon anD oPeratIon manual 25-15049-G October 2021 www.eaton.com...
  • Page 54: Locate Device

    The mode is accessed through user access level 3 (engineer). 1. Select ‘Commissioning’ from the main menu. xDetect 23/8/21 19:09 Panel 2 Alarm Count: 0 Reset Evacuate Silence/ Enable/ View Data Resound Disable Event Log Settings Tests Computer Commissioning InStallatIon anD oPeratIon manual 25-15049-G October 2021 www.eaton.com...
  • Page 55 The LED/output transducer shall remain activated until cancelled. A located device may be cancelled at any time. Returning to the locate device screen, and de-selecting the highlighted device button. The device locate activity shall cease. InStallatIon anD oPeratIon manual 25-15049-G October 2021 www.eaton.com...
  • Page 56: Rapid Faults

    Event Log Settings Tests Computer Commissioning 2. Select ‘rapid Faults’ from the commissioning menu. xDetect 23/8/21 19:09 Panel 2 Alarm Count: 0 Auto-Learn Rapid Faults Loop Status LED Comfort Locate Device Mode InStallatIon anD oPeratIon manual 25-15049-G October 2021 www.eaton.com...
  • Page 57 The displayed fault count shall increment for each fault detected. Rapid fault mode may be terminated at any time. Select the cancel button ends the rapid faults mode and normal fault monitoring resumes. InStallatIon anD oPeratIon manual 25-15049-G October 2021 www.eaton.com...
  • Page 58: User Management - Definitions Of Access Levels

    7. Event Logs 8. Computer 9. System Settings 10. Manage Users Access Level 3 A level 3 user has access to all the functionality of 2, as well as: 1. Commissioning 2. Enable/Disable (all) InStallatIon anD oPeratIon manual 25-15049-G October 2021 www.eaton.com...
  • Page 59: Manage Users

    9999 9999 9999 xDetect 23/8/21 19:09 Panel 2 Alarm Count: 99999 Choose User Engineer Username 1 Username 2 Username 3 Username 4 Username 5 Username 6 Username 7 Username 8 Username 9 InStallatIon anD oPeratIon manual 25-15049-G October 2021 www.eaton.com...
  • Page 60 On selecting Change Username in the Manage Users first screen, the user can then change the username. 9999 9999 9999 9999 9999 xDetect 23/8/21 19:09 Panel 2 Alarm Count: 99999 Current Username Username 1 Enter New Username ‘ New_Username_2 InStallatIon anD oPeratIon manual 25-15049-G October 2021 www.eaton.com...
  • Page 61 Enter New PIN for Username 1 The last 5 PIN’s for all users is stored to prohibit historical PIN re-use, meaning the PIN cannot be changed to one of the previous 5. InStallatIon anD oPeratIon manual 25-15049-G October 2021 www.eaton.com...
  • Page 62 If the PIN is acceptable, the PIN is updated. 9999 9999 9999 9999 9999 xDetect 23/8/21 19:09 Panel 2 Alarm Count: 99999 PIN Updated The PIN is then updated and User is returned to the first Manage Users screen. InStallatIon anD oPeratIon manual 25-15049-G October 2021 www.eaton.com...
  • Page 63 Change Access Levels Level 2 permissions Level 3 permissions Logged Events Each failed login attempt will be logged as a fault in the event log. This includes time, date, and user data. InStallatIon anD oPeratIon manual 25-15049-G October 2021 www.eaton.com...
  • Page 64: Commissioning The System Using Xdetectworks Software

    If not, all Microsoft downloads can be found at http://www.microsoft.com/downloads/. While the software is backwards compatible with .Net 4.0. , it is ote: recommended for stability reasons that it is only run on .Net 4.7 .2 and higher. InStallatIon anD oPeratIon manual 25-15049-G October 2021 www.eaton.com...
  • Page 65: Getting Started

    Start Menu > Programs > xDetectWorks folder and selecting xDetectWorks. Software license Key A license is required to use the xDetectWorks software. Please contact Eaton support and obtain a new license key. The purpose of licensing the software is to ensure that it is used by authorised trained users and that it is updated at regular intervals.
  • Page 66: Configuring A Site

    ‘unnamed’. This is the default root of the entire configuration. To provide a meaningful name, you can edit the properties of the root in the properties area. InStallatIon anD oPeratIon manual 25-15049-G October 2021 www.eaton.com...
  • Page 67: Sites

    By default this will be the same as the details set in the Site properties, but for multi-network sites, you may want to customise this information per network. InStallatIon anD oPeratIon manual 25-15049-G October 2021 www.eaton.com...
  • Page 68: Retrieving Panel Configuration

    8. When the transfer begins, it will open a transfer window that tracks the progress of the files being received over USB. Please note it may take some time to receive all the data. InStallatIon anD oPeratIon manual 25-15049-G October 2021 www.eaton.com...
  • Page 69: Retrieving Configuration - Important Notes

    For this reason, the user should be careful to avoid downloads from panels if the matrix or group data has been modified. Ideally, the user should avoid downloads from panel networks after they are fully commissioned. InStallatIon anD oPeratIon manual 25-15049-G October 2021 www.eaton.com...
  • Page 70: Updating Panels Configuration

    As mentioned previously, this should be done after each panel and module has been fully auto-learned. InStallatIon anD oPeratIon manual 25-15049-G October 2021 www.eaton.com...
  • Page 71: Networks

    All these values are factored into the panel and loop calculation results that provide a guide on how you can expect the panel to perform. InStallatIon anD oPeratIon manual 25-15049-G October 2021 www.eaton.com...
  • Page 72: Modules

    • communication details of the port. ethernet - This port only allows you to configure the connection type. • uSB - This port only allows you to configure the connection type. • InStallatIon anD oPeratIon manual 25-15049-G October 2021 www.eaton.com...
  • Page 73: Programmable Io

    Please Note: This feature is not yet fully supported. This defines a channel as an output based on relay contacts. Volt-Free Output The contacts simply short or open the terminals hence volt-free. InStallatIon anD oPeratIon manual 25-15049-G October 2021 www.eaton.com...
  • Page 74: Conventional Sounder

    By using the zoom option slider bar near the bottom right of the grid, you can adjust the scale of the cells to suit your computer resolution. Larger cells can display more information, where smaller cells will show less information. InStallatIon anD oPeratIon manual 25-15049-G October 2021 www.eaton.com...
  • Page 75: Ld800 Properties

    Filter - If a device has more than one input or output, then this option allows you • to select what input or output you want to display and edit. InStallatIon anD oPeratIon manual 25-15049-G October 2021 www.eaton.com...
  • Page 76: Adding Devices

    It is also possible to insert a gap into the middle of the loop, affectingly increasing the address of all devices that come after it. You can perform an insert with the following steps: - InStallatIon anD oPeratIon manual 25-15049-G October 2021 www.eaton.com...
  • Page 77: Clear Devices

    It should be noted that inputs and outputs can also be utilised for more complex functionality (beyond fire detection and alert). This includes behaviours such as monitoring, control and safety management. InStallatIon anD oPeratIon manual 25-15049-G October 2021 www.eaton.com...
  • Page 78: Concept

    Once you have selected the desired location, you can then add items. To add items, either double click on the appropriate rows or highlight a row and click Add. InStallatIon anD oPeratIon manual 25-15049-G October 2021 www.eaton.com...
  • Page 79: Zones

    Add Alarm Zone. The new Alarm Zone will be created and selected, the property panel will allow you to configure the Name and Zone Number. 12.9.3 Safety Zones These zones are reserved for future functionality and as yet have no purpose. InStallatIon anD oPeratIon manual 25-15049-G October 2021 www.eaton.com...
  • Page 80: Zc Zones

    There will be many devices, inputs or outputs that have the same configuration (sounder volume, input type…etc). If the user wishes, they can group related items together into a configuration group. Here, you can override and modify InStallatIon anD oPeratIon manual 25-15049-G October 2021 www.eaton.com...
  • Page 81: Sector

    If the cause and effect programming for a site is complicated, then the user has the option of creating multiple matrix elements to encapsulate certain parts of the configuration. However, a simple site should only ever need a single matrix. InStallatIon anD oPeratIon manual 25-15049-G October 2021 www.eaton.com...
  • Page 82: Creating A Matrix

    Investigation Delay configured by the Panel’s properties. type C - This enables Dependency Type C mode. This mode means that 2 • independent fire signals from the chosen sources are required to activate the outputs. InStallatIon anD oPeratIon manual 25-15049-G October 2021 www.eaton.com...
  • Page 83 However, binding as a group means that all cells share the same binding properties. This can be useful if you want all the outputs to behave in the same way. InStallatIon anD oPeratIon manual 25-15049-G October 2021 www.eaton.com...
  • Page 84: Common Setups

    5. For all the Alarm Zones that will activate from any source, create a binding between Network - Any/All and each appropriate Alarm Zone. 6. For the each of the other Alarm Zones, bind only the Detection Zones that should activate it. InStallatIon anD oPeratIon manual 25-15049-G October 2021 www.eaton.com...
  • Page 85: Earth Fault Monitoring

    Where a panel is networked with other panels it will be necessary to initiate a soft reset after all the panels have been powered up and this is in order to ensure that they are all synchronised and all faults have been cleared. InStallatIon anD oPeratIon manual 25-15049-G October 2021 www.eaton.com...
  • Page 86: Hard Reset

    10. Hard reset the panel. 11. The panel may now be re-commissioned using xDetectWorks. This process will erase all CDR data from the panel. xDetectWorks must be ote: used to re-commission the panel. InStallatIon anD oPeratIon manual 25-15049-G October 2021 www.eaton.com...
  • Page 87: Commissioning Appendix

    Press the hard reset button on the gateway card ( See Figure 22 on page 31). Unable to soft reset the panel This will necessitate a soft reset on all other networked panels. InStallatIon anD oPeratIon manual 25-15049-G October 2021 www.eaton.com...
  • Page 88: Testing

    Panel 2 Alarm Count: 5 Alarm Count: 5 Tests Tests Panel Weekly Test Walk Test Sound Level Panel Weekly Test LED Test LED Test Test Test Zone Loop Analogue PSU Monitor Values InStallatIon anD oPeratIon manual 25-15049-G October 2021 www.eaton.com...
  • Page 89 The panel LED test may be terminated at any time. Selecting the cancel button prompts the user to confirm exit from the test mode. On exit from the test mode, any previous LED indications are re-instated. A log record for the test event is created. InStallatIon anD oPeratIon manual 25-15049-G October 2021 www.eaton.com...
  • Page 90: Weekly Test

    Panel 2 Alarm Count: 5 Alarm Count: 5 Tests Tests Panel Weekly Test Walk Test Panel Weekly Test Sound Level LED Test Test LED Test Test Zone Loop Analogue PSU Monitor Values InStallatIon anD oPeratIon manual 25-15049-G October 2021 www.eaton.com...
  • Page 91 LED, and all sounder/beacon devices in all zones, for 3 seconds, after which the output devices are deactivated and the test for that zone is complete. If required, further test’s may be performed. InStallatIon anD oPeratIon manual 25-15049-G October 2021 www.eaton.com...
  • Page 92 6. The weekly test may be terminated at any time. Selecting the confirm button prompts the user to confirm exit from the test mode. xDetect 23/8/21 19:09 Panel 2 Alarm Count: 5 Weekly Test Exit Weekly Test? Note: PANEL WILL PERFORM A RESET InStallatIon anD oPeratIon manual 25-15049-G October 2021 www.eaton.com...
  • Page 93: Walk Test

    8. Select ‘Walk test’ from the test menu. xDetect 23/8/21 19:09 Panel 2 Alarm Count: 5 Tests Panel Weekly Test Walk Test Sound Level LED Test Test Test Zone Loop Analogue PSU Monitor Values InStallatIon anD oPeratIon manual 25-15049-G October 2021 www.eaton.com...
  • Page 94 LED, and all sounder/beacon devices in all zones, for 3 seconds, after which the output devices are deactivated and the test for that zone is complete. If required, further tests may be performed. InStallatIon anD oPeratIon manual 25-15049-G October 2021 www.eaton.com...
  • Page 95 13. The walk test may be terminated at any time. Select cancel button prompts the user to confirm exit from the test mode. xDetect 23/8/21 19:09 Panel 2 Alarm Count: 5 Walk Test Exit Walk Test? Note: PANEL WILL PERFORM A RESET InStallatIon anD oPeratIon manual 25-15049-G October 2021 www.eaton.com...
  • Page 96: Zone Test

    Weekly Test Walk Test Sound Level LED Test Test Test Zone Loop Analogue PSU Monitor Values A screen prompting for zone selection is displayed. Any number of zones may be placed into test. InStallatIon anD oPeratIon manual 25-15049-G October 2021 www.eaton.com...
  • Page 97 The zone remains in test and, if required, further test’s may be performed. 4. Select top-bar test button to display current test details. xDetect 23/8/21 19:09 Panel 2 Alarm Count: 5 Zone Test InStallatIon anD oPeratIon manual 25-15049-G October 2021 www.eaton.com...
  • Page 98 All zones removed from test. A log record for each test event is created, indicating the zone test start, activation and termination. xDetect 23/8/21 19:09 Panel 2 Alarm Count: 5 Zone Test InStallatIon anD oPeratIon manual 25-15049-G October 2021 www.eaton.com...
  • Page 99: Sounder Test

    Weekly Test Walk Test Sound Level LED Test Test Test Zone Loop Analogue PSU Monitor Values 3. A screen prompt to begin a sounder test is displayed. Select the confirm button to begin. InStallatIon anD oPeratIon manual 25-15049-G October 2021 www.eaton.com...
  • Page 100: Automatic Smoke Detector Test

    (initial smoke charge, ambient air movement, device mounting etc.) on exiting the test state, sufficient residual smoke may exist to allow the device to enter the alarm condition. InStallatIon anD oPeratIon manual 25-15049-G October 2021 www.eaton.com...
  • Page 101: Delays

    While delay timers can be toggled on/off from the panel HMI, they must be ote: configured via xDetectworks. For more information on specific delays, see “3.2 Optional Functions” on page 11 and “16. Fire Overview Screen” on page 113. InStallatIon anD oPeratIon manual 25-15049-G October 2021 www.eaton.com...
  • Page 102: Disablements

    2. The disablements menu is displayed. xDetect 23/8/21 19:09 Panel 2 Alarm Count: 0 Enable / Disable Input Input Panel Output Output Addresses Zones Circuits Addresses Zones Enable Fire Disable Fire Alarm Devices Alarm Devices InStallatIon anD oPeratIon manual 25-15049-G October 2021 www.eaton.com...
  • Page 103: Enable/Disable Input Or Output Addresses

    2. Select the Loop on which you wish to enable/disable addresses. xDetect 23/8/21 19:09 Panel 1 Alarm Count: 0 Loops 3. Select address to enable or disable. xDetect 23/8/21 19:09 Panel 1 Alarm Count: 0 Enable / Disable: Input Addresses Loop1 InStallatIon anD oPeratIon manual 25-15049-G October 2021 www.eaton.com...
  • Page 104: Enable/Disable Input Or Output Zones

    Circuits Addresses Zones Enable Fire Disable Fire Alarm Devices Alarm Devices 2. Select zone to enable or disable. xDetect 23/8/21 19:09 Panel 1 Alarm Count: 0 Enable / Disable: Input Addresses Loop1 InStallatIon anD oPeratIon manual 25-15049-G October 2021 www.eaton.com...
  • Page 105: Enable/Disable Panel Circuits

    Addresses Zones Enable Fire Disable Fire Alarm Devices Alarm Devices 2. Select zone to enable or disable. xDetect 23/8/21 19:09 Panel 1 Alarm Count: 0 Cards Gateway 1 Sounder 1 I/O 1 InStallatIon anD oPeratIon manual 25-15049-G October 2021 www.eaton.com...
  • Page 106: Enable All Fire Alarm Devices

    19:09 Panel 2 Alarm Count: 0 Enable / Disable Input Input Panel Output Output Addresses Zones Circuits Addresses Zones Enable Fire Disable Fire Alarm Devices Alarm Devices 2. Select the ‘confirm’ button. InStallatIon anD oPeratIon manual 25-15049-G October 2021 www.eaton.com...
  • Page 107: Disable All Fire Alarm Devices

    19:09 Panel 2 Alarm Count: 0 Enable / Disable Input Input Panel Output Output Addresses Zones Circuits Addresses Zones Enable Fire Disable Fire Alarm Devices Alarm Devices 2. Select the ‘confirm’ button. InStallatIon anD oPeratIon manual 25-15049-G October 2021 www.eaton.com...
  • Page 108: Enable/Disable Fpe

    Circuits Addresses Zones Enable Fire Disable Fire Alarm Devices Alarm Devices 2. Select ‘enable FPe’ to enable all FPE on the panel. Select ‘Disable FPe’ to disable all FPE on the panel. InStallatIon anD oPeratIon manual 25-15049-G October 2021 www.eaton.com...
  • Page 109 Enable / Disable FPE Enable FPE Disable FPE 3. Select the ‘confirm’ button. xDetect 23/8/21 19:09 Panel 1 Alarm Count: 0 Enable FPE Warning! This will enable all FPE on this panel. InStallatIon anD oPeratIon manual 25-15049-G October 2021 www.eaton.com...
  • Page 110: Enable/Disable Fre

    2. Select ‘enable Fre’ to enable all FRE on the panel. Select ‘Disable Fre’ to disable all FRE on the panel. xDetect 23/8/21 19:09 Panel 1 Alarm Count: 0 Enable / Disable FRE Enable FRE Disable FRE InStallatIon anD oPeratIon manual 25-15049-G October 2021 www.eaton.com...
  • Page 111: Enable/Disable Fwre (Gateway)

    1. Select ‘Panel Circuits’ from the disablements menu. xDetect 23/8/21 19:09 Panel 2 Alarm Count: 0 Enable / Disable Input Input Panel Output Output Addresses Zones Circuits Addresses Zones Enable Fire Disable Fire Alarm Devices Alarm Devices InStallatIon anD oPeratIon manual 25-15049-G October 2021 www.eaton.com...
  • Page 112 Sounder 1 I/O 1 3. Use checkbox to enable or disable Gateway 1. xDetect 23/8/21 19:09 Panel 1 Alarm Count: 0 Cards Circuit Configuration Gateway 1 Circuit 1 Fault Output (Volt Mon.) InStallatIon anD oPeratIon manual 25-15049-G October 2021 www.eaton.com...
  • Page 113: Fire Overview Screen

    Call point override (option not required by en54 pt2) This is similar to the above except a call point alarm will activate the output instantly. InStallatIon anD oPeratIon manual 25-15049-G October 2021 www.eaton.com...
  • Page 114 This section shows details of all fires currently active in the zone. Use arrows on right to scroll through the list Use the back action button to go back to fire overview screen. InStallatIon anD oPeratIon manual 25-15049-G October 2021 www.eaton.com...
  • Page 115: Faults Overview Screen

    Alarm Count: 0 Fault Details Service Company Date: 16/08/21 Test Installer Time: 14:29 Panel: 1 Module: 1 Fault: Loop Device Missing Telephone Number Address 5 Device Type: Interface 01234 567890 Zone: 2 InStallatIon anD oPeratIon manual 25-15049-G October 2021 www.eaton.com...
  • Page 116: Event Log

    1. Log in at user access level 2 (or higher). 2. Select ‘event log’ on the main menu. xDetect 23/8/21 19:09 Panel 2 Alarm Count: 5 Reset Evacuate Silence/ Enable/ View Data Resound Disable Event Log Settings Tests Computer Commissioning InStallatIon anD oPeratIon manual 25-15049-G October 2021 www.eaton.com...
  • Page 117 16/08/21 14:57 Sounder 1 Circuit 2 Open Circuit 16/08/21 14:53 Gateway 1 Alarm Zone 1 Enabled 16/08/21 14:34 Loop 1 Device Enabled. Addr 3 16/08/21 11:10 Gateway 1 Alarm Zone 2 Enabled InStallatIon anD oPeratIon manual 25-15049-G October 2021 www.eaton.com...
  • Page 118: Evacuation

    Enable/ View Data Resound Disable Event Log Settings Tests Computer Commissioning 2. Select the ‘confirm’ button to perform a system evacuation. xDetect 23/8/21 19:09 Panel 1 Alarm Count: 0 Evacuate Evacuate System? InStallatIon anD oPeratIon manual 25-15049-G October 2021 www.eaton.com...
  • Page 119: Silence/Resound Alarms

    2. Select ‘Silence’ to silence all alarms on the system. Select ‘resound’ to enable and sound all alarms on the system. xDetect 23/8/21 19:09 Panel 2 Alarm Count: 5 Silence/ Resound Silence Resound Sound Options InStallatIon anD oPeratIon manual 25-15049-G October 2021 www.eaton.com...
  • Page 120 5. Use checkbox to enable or disable resound in new zones only. xDetect 23/8/21 19:09 Panel 2 Alarm Count: 5 Zone Sound Options Resound for activations in new zones only If option is deselected, sounders will resound for all activations InStallatIon anD oPeratIon manual 25-15049-G October 2021 www.eaton.com...
  • Page 121: Maintenance

    If no devices are triggered during the weekly test the panel will abort the test and reset after 5 mins. Record weekly test in the table provided in this log book InStallatIon anD oPeratIon manual 25-15049-G October 2021 www.eaton.com...
  • Page 122: Non Routine

    22. Supported Languages xDetect supports multiple languages, the availibility of which will depend on the installed language pack(s). English is included as standard - to order additional languages packs, please contact Eaton. InStallatIon anD oPeratIon manual 25-15049-G October 2021 www.eaton.com...
  • Page 123 15.6, 15.7, 15.15 9.7, 9.8, 9.15 Vibration Resistance Durability Of Operational Reliability, Pass 15.8 to 15.13 9.9 to 9.13 Electrical Stability Durability Of Operational Reliability, Pass 15.5, 15.14 9.6, 9.14 Humidity Resistance InStallatIon anD oPeratIon manual 25-15049-G October 2021 www.eaton.com...
  • Page 124 Firesales@eaton.com Firetechsupport@eaton.com © 2021 Eaton Eaton Electrical Products Ltd. All Rights Reserved. Llantarnam Park Eaton is a registered trademark. Cwmbran NP44 3AW All trademarks are property of their Tel: +44 (0) 1633 628500 respective owners. Fax: +44 (0) 1633 866346 www.eaton.com...

This manual is also suitable for: