Mitsubishi Electric PUH-P200MYA Technical & Service Manual page 31

Air-cooled split-type packaged air conditioners
Hide thumbs Also See for PUH-P200MYA:
Table of Contents

Advertisement

<Outdoor unit operation monitoring function>
The operation status and check code contents can be ascertained by means of the 2-digit number and symbol on digital
display light emitting diode LED2 by operating DIP switch SW2.
<Description of operation of digital display light emitting diode (LED2)>
• When ON (normal operation): Displays the operation mode.
[Tens digit: Operation mode]
Display
Operation mode
O
stopped
C
Cooling/Dry
H
Heating
d
Defrost
• When blinking (Operation stopped by tripping protection device): Displays the check mode
Display
Check unit
0
Outdoor unit
1
Indoor unit 1
2
Indoor unit 2
3
Indoor unit 3
4
Indoor unit 4
PUH-P8MYA/P10MYA
Display
U2
Compressor discharge temperature abnormal, CN23 short-circuit connector unplugged
U3
Compressor discharge temp thermistor (TH2) open/short
U4
Liquid temp thermistor (TH1), Condenser/evaporater temp thermistor (TH3) open/short
U6
Compressor overcurrent protection trip (51C trip)
UE
High pressure protection (63H1 trip)
UL
Low pressure protection (63L trip)
P1-P8
Indoor unit abnormal
A0-A8
M-NET communication abnormal
ON
LED2
[Units digit: Relay output]
Display
0
1
2
3
4
5
6
7
Display
E8
Indoor-outdoor communication receive abnormal (outdoor unit)
E9
Indoor-outdoor communication send abnormal (outdoor unit)
Indoor/outdoor connection erroneous wiring, number of indoor
EA
units mismatch
Indoor/outdoor connection erroneous wiring (indoor unit power
Eb
failure, disconnection)
Ed
Serial communication abnormal (M-NET)
E0-E7
Communication other than outdoor unit abnormal
F8
Input circuit faulty
Check contents (operating)
–29–
SW2
1 2 3 4 5 6
ON
OFF
(Load status)
Compressor
4-way valve
ON
ON
ON
ON
ON
ON
ON
ON
Check contents (at power on)
Bypass solenoid valve
ON
ON
ON
ON