Technical Data Of Puh-P200Mya/P250Mya To Meet Lvd; Standard Operation Data - Mitsubishi Electric PUH-P200MYA Technical & Service Manual

Air-cooled split-type packaged air conditioners
Hide thumbs Also See for PUH-P200MYA:
Table of Contents

Advertisement

5 Technical Data of PUH-P200MYA/P250MYA to Meet LVD

[1] Standard Operation Data

(1) PUH-P200MYA
Operating condition
Voltage
Power source frequency
Indoor air condition (DB/WB)
Outdoor air condition (DB/WB)
Piping length
Refrigerant charge
Current
Input
Outdoor unit
Compressor current
Fan current
Current
Indoor unit
Input
Discharge pressure
Suction pressure
Discharge refrigerant temperature
Suction refrigerant temperature
Liquid pipe temperature (at piping sensor)
Compressor shell bottom temperature
Note: The values listed above indicate that when connected with the indoor unit PEH-RP200MYA as representative data.
(2) PUH-P250MYA
Operating condition
Voltage
Power source frequency
Indoor air condition (DB/WB)
Outdoor air condition (DB/WB)
Piping length
Refrigerant charge
Current
Input
Outdoor unit
Compressor current
Fan current
Current
Indoor unit
Input
Discharge pressure
Suction pressure
Discharge refrigerant temperature
Suction refrigerant temperature
Liquid pipe temperature (at piping sensor)
Compressor shell bottom temperature
Note: The values listed above indicate that when connected with the indoor unit PEH-RP250MYA as representative data.
Cooling
V
380
400
Hz
50
50
°C
27/19
27/19
°C
35/–
35/–
m
7.5
7.5
kg
7.9
7.9
A
13.0
13.0
kW
7.27
7.27
A
11.9
11.9
A
1.1
1.1
A
1.12
1.12
kW
0.65
0.65
MPa
2.11
2.11
MPa
0.48
0.48
°C
75
75
°C
6
6
°C
46
46
°C
35
35
Cooling
V
380
400
Hz
50
50
°C
27/19
27/19
°C
35/–
35/–
m
7.5
7.5
kg
8.4
8.4
A
16.0
16.0
kW
9.02
9.02
A
14.9
14.9
A
1.1
1.1
A
1.64
1.64
kW
0.94
0.94
MPa
2.22
2.22
MPa
0.50
0.50
°C
80
80
°C
8
8
°C
48
48
°C
30
30
–13–
Heating
415
380
400
50
50
50
27/19
20/–
20/–
35/–
7/6
7/6
7.5
7.5
7.5
7.9
7.9
7.9
13.0
12.8
12.8
7.27
7.17
7.17
11.9
11.7
11.7
1.1
1.1
1.1
1.12
1.12
1.12
0.65
0.65
0.65
2.11
1.91
1.91
0.48
0.40
0.40
75
70
70
6
0
0
46
0
0
35
30
30
Heating
415
380
400
50
50
50
27/19
20/–
20/–
35/–
7/6
7/6
7.5
7.5
7.5
8.4
8.4
8.4
16.0
15.4
15.4
9.02
8.62
8.62
14.9
14.3
14.3
1.1
1.1
1.1
1.64
1.64
1.64
0.94
0.94
0.94
2.22
1.75
1.75
0.50
0.38
0.38
80
65
65
8
-1
-1
48
0
0
30
20
20
415
50
20/–
7/6
7.5
7.9
12.8
7.17
11.7
1.1
1.12
0.65
1.91
0.40
70
0
0
30
415
50
20/–
7/6
7.5
8.4
15.4
8.62
14.3
1.1
1.64
0.94
1.75
0.38
65
-1
0
20

Advertisement

Table of Contents
loading

This manual is also suitable for: