Information About Refrigerant; Important Information: Regulation Regarding The Refrigerant Used - Samsung AC100RN4PKG/EU User Manual

Table of Contents

Advertisement

Information about refrigerant

Important information: regulation regarding the refrigerant used

This product contains fluorinated greenhouse gases. Do not vent gases into the atmosphere.
CAUTION
If the system contains 5 tCO₂e or more of fluorinated greenhouse gases, it must be checked
for leakage at least once every 12 months, according to regulation No. 517/2014. This
activity must be covered by qualified personnel only. In the case of the situation above,
the installer (or authorized person with responsibility for final check) must provide a
maintenance book, with all the information recorded, according to REGULATION (EU) No.
517/2014 OF THE EUROPEAN PARLIAMENT AND OF THE COUNCIL of 16 April 2014 on
fluorinated greenhouse gases.
This indoor unit can be connected to an R-32 or R-410A outdoor unit.
– R-32 - Single / DPM
– R-410A - DPM only (available with AC200/250KXAPNH)
Refrigenat type
R-32
R-410A
GWP: Global Warming Potential
Calculating tCO₂e: kg x GWP/1000
GWP value
675
2088
19