Maintenance Plan - ABB AMD Rg 355 Installation, Operation And Maintenance Instructions

High voltage flameproof motors for explosive gas atmospheres
Table of Contents

Advertisement

Installation, operation and maintenance instructions

High voltage flameproof motors for explosive atmosphere
AMD Rg 355-400-450-500

Maintenance plan

Part of
machine
Foundation and
basement
Coupling joint
Whole machine
Bearings
Stator winding
Visual inspection
of machine inside
and outside
Main terminal box
REMARK: at reassembling of box cover smear the surfaces of the flame joint with the prescribed silicon grease
Auxiliaries terminal
boxes.
REMARK: at reassembling of box cover smear the surfaces of the flame joint with the prescribed silicon grease
Fan drive motor
and fittings
(if provided)
1)
Compare with previous measurements and observations.
2)
In case of vibration level increase, inspect as soon as possible and increase the check frequency.
3)
Remove rust. Select method and means to suit the component involved.
REMARK : always check that the flame tightness joints dimensions remain into the prescribed
tolerances and with the prescribed surface rugosity!
Maintenance or inspection work
Check tightness of machine foundation bolts and state of
locking elements.
Check state of alignment of the coupling and record
measurements.
Maintenance of coupling in accordance with coupling
manufacturer's instructions
Pay attention to unusual machine noise or change in
noise (e.g. rubbing or knocking sounds, etc.).
Visually check the degree of dirt deposit inside the
machine.
See relevant maintenance sheets according to the type of bearings
(vibration level control is contained in these sections)
Measure temperature at provided measuring points
( e.g., built-in RTD's).
Measure dielectric resistance.
Dielectric condition diagnosis.
Visual check at all accessible points for rust.
Visual check for cleanness and absence of moisture from
condensation
Check for tightness and state of conductors, terminals
and locking elements
Visual check for cleanness and absence of moisture from
condensation
Check conditions and fastening of all supply cables and
connections.
Visual inspection for rust and dirt
Check of vibration level
Sheet No
3AAM101038 E
Rev. B
01.2023
Page 1 of 1
2)
1)
1)
1)
3)
3)
Issued by: MOLM

Advertisement

Table of Contents
loading

This manual is also suitable for:

Amd rg 400Amd rg 450Amd rg 500

Table of Contents