Unit Shuts Down in 15‐20
minutes with an "FS" code
(Top Mount) or "E‐2" code
(Side Mount) on control
board. (Failed Start)
"OT" Code (Top Mount) or
"E‐3" Code (Side Mount) on
Control Board (OverTemp)
Notes:
1. Whenever instructed to check/replace the vacuum sensor, also check for loose or cracked vacuum hose.
Also, be certain the vacuum measurement port in the firebox is kept clean (clean with a pipe cleaner or brush,
do not use a vacuum to clean this port).
2. To restart and clear an error code displayed on the control board, push the "ON" button and the unit should
reset the error and restart.
3. If you are uncertain about the meaning of an error code or have any questions at all, PLEASE contact
Technical Support at (800)245‐6489.
IMPORTANT SAFETY NOTE: If the unit or chimney connector pipe "glows" red (or
white), the stove is over-fired. This condition could cause a house or chimney fire.
Do not operate your unit too hot, or over-firing may result.
IMPORTANT! READ AND FOLLOW ALL INSTALLATION AND MAINTENANCE INSTRUCTIONS, INCLUDING CLEANING THE UNIT AS SPECIFIED, AND
ENGLAND'S STOVE WORKS IS NOT RESPONSIBLE FOR ANY DAMAGE OR INJURY INCURRED DUE TO NEGLECT, OR DUE TO UNSAFE INSTALLATION OR
Error codes related only to side mounted control board
1. Loose thermal sensor.
2. Control board settings.
3. Failure to light pellets.
1. Convection (Room Air) blower
failure.
2. Partially blocked flue.
3. Using fuel other than premium wood
pellets.
REPLACING GASKETS ANNUALLY, AND PARTS AS NEEDED.
USAGE OF THIS PRODUCT. CALL TECHNICAL SUPPORT WITH ANY QUESTIONS.
1. Check both sides of thermal sensor
connection (exhaust blower and control
board).
2. Start stove on minimum Heat Range 5 to
ensure a good fire is started.
3. Check igniter for buildup or failure.
1. Check convection blower for proper
function, replace if necessary.
2. Check flue for obstructions.
3. Use ONLY premium wood pellets in this
stove.
42